14
YASKAWA
SIEP C730600 0IB Modbus TCP/IP Technical Manual
Note:
Isolate communication cables from main circuit wiring and other electrical and power lines.
A - Route wires through the openings provided on
the left side of the front cover.
B - Use the open space provided inside the drive to
route option wiring.
Figure 5.4 Wire Routing Examples
*1
If there is wiring outside the enclosure, the drive will not meet Enclosed wall-mounted type (IP20/UL Type 1)
requirements.
7.
Firmly connect the Ethernet communication cables to CN1B (Port 2) (J), and/or CN1A (Port 1) (K).
Isolate communication cables from main circuit wiring and other electrical and power lines. Make sure that
you firmly connect the cable end. Refer to
Communication Cable Specifications on page 19
for more
information.
8.
Reattach the front cover (C), terminal cover (F), and keypad (D).
Refer to the drive manuals for more information.
NOTICE
Do not pinch cables between the front covers and the drive. Failure to comply could cause
erroneous operation.
9.
Set drive parameters in
Related Drive Parameters on page 20
for correct option performance.
■
Procedure B
This section shows the procedure to install and wire the option on a Z1000 drive.
Prepare the Drive for the Option
Correctly wire the drive as specified by the manual packaged with the drive. Make sure that the drive functions
correctly. Refer to the drive manuals for more information.