H1-
oo
Setting
Function
LCD Display
Description
Page
90
High Water Level
High Water
Function active when the drive is running. Function logic depends on P1-31, High
Water Digital Input Configuration.
P1-31 = 0 (Normally open)
Closed: High water level fault
Open: Reservoir/Tank is filled to normal level
P1-31 = 1 (Normally closed)
Closed: Reservoir/Tank is filled to normal level
Open: High water level fault
95
Remove Drive Disable Remote Drv Disbl
Closed: Prevents the drive from running when active for the time set in P4-26.
Must be inactive for the time set in P4-27 to allow the drive to run again.
Note:
1. Parameter P4-25 determines if this input is normally open or
normally closed.
2. When P1-01 = 3, an alarm condition will cause this drive to be
unavailable to the network.
AF
Emergency Override
Forward Run
EmergOverrideFWD Closed: Run the drive forward using the speed set in S6-02.
B0
Emergency Override
Reverse Run
EmergOverrideREV Closed: Run the drive in reverse using the speed set in S6-02.
u
H2: Multi-Function Digital Outputs
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
H2-01
(040B)
Terminal MA, MB, and
MC function selection
(relay)
MA/MB/MC FuncSel
Refer to H2 Multi-Function Digital Output Settings on pages
for descriptions of setting values.
Default: E
Range: 0 to 1AA
H2-02
(040C)
Terminal P1 function
selection (open-
collector)
P1/PC Func Sel
Default: 37
Range: 0 to 1AA
H2-03
(040D)
Terminal P2 function
selection (open-
collector)
P2/PC Func Sel
Default: E
Range: 0 to 1AA
H2-06
(0437)
Watt Hour Output Unit
Selection
Pwr Mon Unit Sel
Outputs a 200 ms pulse signal when the watt-hour counter
increases by the units selected.
0: 0.1 kWh units
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
Default: 0
Range: 0 to 4
Table B.3 H2 Multi-Function Digital Output Settings
H2-
oo
Setting
Function
LCD Display
Description
Page
0
During run
During RUN 1
Closed: A Run command is active or voltage is output.
1
Zero speed
Zero Speed
Open: Output frequency is above the minimum output frequency set in E1-09.
Closed: Output frequency is below the minimum output frequency set in E1-09.
2
Speed agree 1
Fref/Fout Agree1
Closed: Output frequency equals the speed reference (plus or minus the hysteresis
set to L4-02).
3
User-set speed agree 1 Fref/Set Agree 1
Closed: Output frequency and speed reference equal L4-01 (plus or minus the
hysteresis set to L4-02).
4
Frequency detection 1 Freq Detect 1
Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis
determined by L4-02.
5
Frequency detection 2 Freq Detect 2
Closed: Output frequency is greater than or equal to the value in L4-01 with
hysteresis determined by L4-02.
6
Drive ready
Drive Ready
Closed: Power up is complete and the drive is ready to accept a Run command.
7
DC bus undervoltage
DC Bus Undervolt
Closed: DC bus voltage is below the Uv trip level set in L2-05.
8
During baseblock
(N.O.)
BaseBlk 1
Closed: Drive has entered the baseblock state (no output voltage).
B.8 H Parameters: Multi-Function Terminals
YASKAWA
TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
339
B
Parameter List