Setting 96: High Feedback
Output terminal closes during a “High Feedback Condition” as defined by P1-11 and P1-14, or during a “High FB / Water”
Fault, or during a “High Feedback” Alarm.
Setting 97: Low Feedback
Output terminal closes during a “Low Feedback Condition” as defined by P1-08 and P1-14, or during a “Low FB/Water”
Fault, or during a “Low Feedback” Alarm.
Setting A2: Sleep Active
Output terminal closes when drive is not running due to the Sleep function (does not include Sleep Boost).
Setting A3: Start Delay
Output terminal closes when feedback has risen above the start level (or fallen below the start level for Inverse PID) and the
start timer is timing.
Setting A4: Pre-Charge
Output terminal closes when the drive is in Pre-Charge mode.
Setting A5: Anti-Jam Active
Detects and expels solids that are preventing the pump impeller from turning.
WARNING!
Sudden Movement Hazard. The Anti-Jam function can force the motor to briefly run in the reverse direction and may cause
injury even if parameter b1-04 is set to “Reverse Disabled”. Be sure all personnel are clear of rotating machinery.
Setting A9: Thrust Mode
Output terminal closes when the Thrust Bearing feature is active (output frequency is between zero and P4-12).
Setting AA: Utility Start Delay
Output terminal closes when the drive is stopped and waiting for the utility delay timer to expire. This setting is configured
by P4-17.
Settings 100 to 1AA: Functions 0 to AA with Inverse Output
These settings have the same function as settings 0 to AA but with inverse output. Set as 1
oo
, where the “1” indicates inverse
output and the last two digits specify the setting number of the function.
Examples:
• For inverse output of “8: During baseblock”, set 108.
• For inverse output of “4A: During KEB” set 14A.
n
H2-06: Watt Hour Output Unit Selection
When one of the multi-function terminals is set to output the number of watt hours (H2-01/02/03 = 39), parameter H2-06
determines the units for the output signal.
The output is intended to drive a watt hour meter or a PLC input by a 200 ms pulse signal. A pulse is output according to the
kWh unit selected in H2-06.
No.
Parameter Name
Setting Range
Default
H2-06
Watt Hour Output Unit Selection
0: 0.1 kWh units
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
0
n
H3-01: Terminal A1 Signal Level Selection
Selects the input signal level for analog input A1.
No.
Name
Setting Range
Default
H3-01
Terminal A1 Signal Level Selection
0, 1
0
Setting 0: 0 to 10 Vdc
The input level is 0 to 10 Vdc. The minimum input level is limited to 0%, so that a negative input signal due to gain and bias
settings will be read as 0%.