• The “Low Feedback” fault is disabled when forward-acting PID is selected (b5-09 = 0) and the “High Feedback” fault is
disabled when reverse-acting PID is selected (b5-09 = 1).
• The “Not Maintaining Setpoint” fault is disabled.
• The “Feedback Loss” detection (4 to 20 mA wire break) is enabled, however, the Pre-Charge frequencies will override and
the b5-13 “feedback loss goto speed”.
The drive will always exit Pre-Charge Mode when Pre-Charge times P4-03 and P4-07 have expired. The drive will also exit
Pre-Charge Mode when one of the following conditions are met:
• P4-03 and P4-32 are set to 0.0
• The “Disable Pre-Charge” digital input (H1-0
o
= 8C) closes.
• A digital input programmed to “Low Water” (H1-0
o
= 8F) is deactivated (open when P1-30 = 0 or closed when P1-30 =
1).
• The PID feedback satisfies both Pre-charge levels 1 and 2 (all must be true):
Pre-charge timers P4-03 and P4-07 have NOT expired
PID is enabled (b5-01 > 0).
PID is NOT disabled via digital input
Pre-Charge Level Set (P4-01 > 0) (and if used, P4-32 > 0)
Feedback is greater than Pre-Charge Level (P4-01) and Pre-charge Level 2 (P4-32) (forward-acting PID, b5-09 = 0) or less
than Pre-Charge Levels 1 and 2 (reverse-acting PID, b5-09 = 1)
Drive is NOT in a “Feedback Loss” condition (4 to 20 mA wire-break detection).
n
P2-04: Sleep Activate Level
When P2-01, Sleep Level Type, is set to 0 (Output Frequency / Speed), the Sleep function activates when the output frequency
is greater or equal to the level set in P2-04. When P2-04 is programmed to 0.0, the Sleep function activates above P2-02, Sleep
Level.
No.
Name
Setting Range
Default
P2-04
Sleep Activate Level
0.0 to 6000.0
0.0 Hz
n
P2-05: Sleep Boost Level
Sets the amount of boost applied to the setpoint prior to going to sleep. A setting of 0.0 disables the sleep boost function.
No.
Name
Setting Range
Default
P2-05
Sleep Boost Level
0.0 to 6000.0
0.0 PSI
n
P2-06: Sleep Boost Hold Time
Sets the amount of time the boosted pressure will be maintained before the drive goes to sleep.
No.
Name
Setting Range
Default
P2-06
Sleep Boost Hold Time
0.5 to 160.0 s
5.0 s
n
P2-07: Sleep Boost Maximum Time
Sets the amount of time the system (feedback) has to reach the boosted setpoint. The drive goes to sleep when the amount of
time set in P2-07 is exceeded.
No.
Name
Setting Range
Default
P2-07
Sleep Boost Maximum Time
0.5 to 160.0 s
5.0 s
n
P2-08: Delta Sleep Feedback Drop Level
When the drive enters sleep mode, the software monitors the feedback to detect a flow-no flow condition. When the PID error
(setpoint minus feedback) exceeds the level set in P2-08 within the time set in P2-09 and the output frequency exceeds the
P1-06 setting, the sleep operation deactivates and the drive returns to normal operation.
No.
Name
Setting Range
Default
P2-08
Delta Sleep Feedback Drop Level
0.0 to 6000.0
0.0 PSI
5.11 P: Pump
230
YASKAWA
TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual