Condition
Freq. Ref.
Source
d4-03 d4-05 d4-01
Operation
Frequency Saved
8
Other (analog
comm, etc.)
0
1
--
• Accelerates (increases the bias) while the Up 2
terminal is closed.
• Decelerates (decreases the bias) while Down 2 is
closed.
• Otherwise operates at the frequency reference
Not saved
9
Value
other
than 0
--
0
• When Up 2 is enabled, drive accelerates to the
frequency reference plus d4-03 (increases the bias
for d4-03).
• When Down 2 is enabled, drive decelerates to the
frequency reference minus d4-03 (decreases the
bias for d4-03).
• If the frequency reference changes for more than
d4-07 during accel/decel, bias value is held until the
output frequency meets the reference (speed agree).
Not saved
10
1
If the bias is constant for 5 s, it is
saved to parameter d4-06. The
frequency reference cannot be
overwritten, so only the bias is
saved.
Settings 7A and 7B: KEB Ride-Thru 2 (N.C., N.O.)
An input terminal set to 7A or 7B can trigger Single Drive KEB Ride-Thru during deceleration. L2-29 is disregarded if this
is enabled.
Digital Input Function
Drive Operation
Input Open
Input Closed
Setting 7A (N.C.)
Single Drive KEB Ride-Thru 2
Normal operation
Setting 7B (N.O.)
Normal operation
Single Drive KEB Ride-Thru 2
Note:
Simultaneously assigning KEB Ride-Thru 1 and KEB Ride-Thru 2 to the input terminals will trigger an oPE03 error.
Setting 80: HAND Mode
Closing this input will put the drive in HAND Mode.
If this contact is closed within one second of power-up, the drive will honor the utility delay time.
Note:
When inputs 80 and 81 are closed simultaneously, input 80 has priority and P5-01 determines the frequency reference.
Setting 81: HAND Mode 2
Closing this input will put the drive in HAND Mode using P5-05 as a frequency reference.
If this contact is closed within one second of power-up, the drive will honor the utility delay time.
Note:
When inputs 80 and 81 are closed simultaneously, input 80 has priority and P5-01 determines the frequency reference.
Settings 83, 84, and 85: Alternate Multi-step Setpoints
These setpoint selections are different from Multi Setpoints 1 and 2 (H1-
oo
= 8D/8E) in that each input is dedicated to a
setpoint instead of being a binary selection.
shows active setpoints based on the Alternate Multi-Setpoint Selections (H1-
oo
= 83 to 85):
Table 5.23 Active Setpoints by H1-
oo
Setting
Alternate Multi-Setpoint Q1-02
H1-
oo
= 83
Alternate Multi-Setpoint Q1-03
H1-
oo
= 84
Alternate Multi-Setpoint Q1-04
H1-
oo
= 85
Setpoint
Open
Open
Open
Q1-01
Closed
Open/Closed
Open/Closed
Q1-02
Open
Closed
Open/Closed
Q1-03
Open
Open
Closed
Q1-04
Setting 88: Volute-Thermostat (N.O.)
Closed: Drive will trip on “VLTS - Volute-TStat Flt”.
Open: Thermostat fault not active.
Note:
Assigning both 88 and 89 to input terminals will trigger a VLTS-Volute-TStat Flt.
Setting 89: Volute-Thermostat (N.C.)
Closed: Thermostat fault not active.
Open: Drive will trip on “VLTS - Volute-TStat Flt”.
Note:
Assigning both 88 and 89 to input terminals will trigger a VLTS-Volute-TStat Flt.
5.7 H: Terminal Functions
172
YASKAWA
TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Содержание iQpump Micro CIMR-PW Series
Страница 443: ......