5.1 A: Initialization Parameters
182
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Table 5.11 Parameters Saved as User Parameters with the Cooling Tower Fan Preset
User Parameter No.
Parameter No. Saved
Name
A2-01
b1-03
Stopping Method Selection
A2-02
b1-04
Reverse Operation Selection
A2-03
b2-09
Pre-heat Current 2
A2-04
b5-01
PID Mode Setting
A2-05
b5-03
Integral Time (I)
A2-06
b5-08
PID Primary Delay Time Constant
A2-07
b5-09
PID Output Level Selection
A2-08
C1-01
Acceleration Time 1
A2-09
d2-03
Analog Frequency Ref Lower Limit
A2-10
H1-07
Terminal S7 Function Selection
A2-11
H3-01
Terminal A1 Signal Level Select
A2-12
H3-02
Terminal A1 Function Selection
A2-13
H3-10
Terminal A2 Function Selection
A2-14
L5-01
Number of Auto-Restart Attempts
A2-15
o1-24
Custom Monitor 1
A2-16
o1-25
Custom Monitor 2
A2-17
o1-26
Custom Monitor 3
A2-18
Y1-04
Sleep Wake-up Level
A2-19
Y1-05
Sleep Wake-up Level Delay Time
A2-20
Y1-08
Low Feedback Level
A2-21
Y1-09
Low Feedback Lvl Fault Dly Time
A2-22
Y2-01
Sleep Level Type
A2-23
Y2-02
Sleep Level
A2-24
Y2-03
Sleep Delay Time
A2-25
Y2-04
Sleep Activation Level
5 : Cooling Tower Fan w/ PID
The drive automatically sets the parameters in
for a cooling tower fan with PID control application.
Table 5.12 Best Parameter Settings for Cooling Tower Fan with PID Control Applications
No.
Name
Optimal Value
A1-02
Control Method Selection
0: V/f Control
b1-03
Stopping Method Selection
1: Coast to Stop
b1-04
Reverse Operation Selection
0: Reverse Enabled
b5-01
PID Mode Setting
1: Standard
b5-03
Integral Time (I)
30.0 s
b5-08
PID Primary Delay Time Constant
2.00 s
b5-09
PID Output Level Selection
1: Reverse Output (Reverse Acting)
C1-01
Acceleration Time 1
60.0 s
H3-10
Terminal A2 Function Selection
B: PID Feedback
L5-01
Number of Auto-Restart Attempts
10
Y1-04
Sleep Wake-up Level
-5.00
Y1-05
Sleep Wake-up Level Delay Time
30 s
Y1-08
Low Feedback Level
2.00%
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...