C: Tuning
◆
C1: Accel & Decel Time
No.
(Hex.)
Name
Description
Default
(Range)
C1-01
(0200)
RUN
Acceleration Time 1
Sets the length of time to accelerate from zero to maximum output frequency.
30.0 s
(0.1 - 6000.0 s)
C1-02
(0201)
RUN
Deceleration Time 1
Sets the length of time to decelerate from maximum output frequency to zero.
30.0 s
(0.1 - 6000.0 s)
C1-03
(0202)
RUN
Acceleration Time 2
Sets the length of time to accelerate from zero to maximum output frequency.
30.0 s
(0.1 - 6000.0 s)
C1-04
(0203)
RUN
Deceleration Time 2
Sets the length of time to decelerate from maximum output frequency to zero.
30.0 s
(0.1 - 6000.0 s)
C1-09
(0208)
RUN
Fast Stop Time
Sets the length of time that the drive will decelerate to zero for a Fast Stop.
Note:
Decelerating too quickly can cause an
ov [Overvoltage]
fault that shuts off the drive while the
motor to coasts to a stop. Set a Fast Stop time in
C1-09
that prevents motor coasting and makes
sure that the motor stops quickly and safely.
10.0 s
(0.1 - 6000.0 s)
◆
C2: S-Curve Characteristics
No.
(Hex.)
Name
Description
Default
(Range)
C2-01
(020B)
S-Curve Time @ Start of
Accel
Sets the S-curve acceleration time at start.
0.20 s
(0.00 - 10.00 s)
C2-02
(020C)
S-Curve Time @ End of
Accel
Sets the S-curve acceleration time at completion.
0.20 s
(0.00 - 10.00 s)
C2-03
(020D)
S-Curve Time @ Start of
Decel
Sets the S-curve deceleration time at start.
0.20 s
(0.00 - 10.00 s)
C2-04
(020E)
S-Curve Time @ End of
Decel
Sets the S-curve deceleration time at completion.
0.00 s
(0.00 - 10.00 s)
◆
C3: Slip Compensation
No.
(Hex.)
Name
Description
Default
(Range)
C3-01
(020F)
RUN
Slip Compensation Gain
Sets the gain for the slip compensation function. Usually it is not necessary to change this setting.
Note:
Correctly set these parameters before you change the slip compensation gain:
•
E2-01 [Motor Rated Current (FLA)]
•
E2-02 [Motor Rated Slip]
•
E2-03 [Motor No-Load Current]
0.0
(0.0 - 2.5)
C3-02
(0210)
RUN
Slip Compensation Delay
Time
Sets the slip compensation delay time when speed is unstable or when the slip compensation
response is too slow. Usually it is not necessary to change this setting.
2000 ms
(0 - 10000 ms)
Содержание HV600
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 20: ...1 2 Catalog Code and Nameplate Check 20 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 34: ...2 7 Removing Reattaching Covers 34 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 40: ...Page Intentionally Blank...
Страница 154: ...5 11 Diagnosing and Resetting Faults 154 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 170: ...6 7 Periodic Inspection and Maintenance 170 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 266: ...7 16 U Monitors 266 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 290: ...8 4 Other Embedded Communication Protocols 290 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...