4 Primary Operation Tests

12

YASKAWA

TOEPYAIH6R01B HV600 REDUNDANT DRIVE OPERATIONAL TEST MANUAL

Confirm Auto-Transfer Function

This test is optional based on the application requirements.

Table 4.4 Confirm Auto-Transfer Function

Check

Step

Details

Figure

16

Set the MAN-FAULT XFER-AUTO switch to

AUTO

.

17

Set the DRV A-AUTO-DRV B switch to

AUTO

.

18

Set the HAND-OFF-AUTO switch to

HAND

to start Drive A.

19

Confirm that you can use the BAS to change the speed reference for Drive A and Drive B.

-

20

If necessary, remove the front cover from Drive A to access the TB3 and TB4 terminal blocks below
the control board.

While Drive A is running, momentarily jumper terminal TB4 SN to TB3 S3 (external fault normally
open) to trigger a fault in Drive A.

Note:

When you jumper terminal SN to S3, Drive A will fault on an

EF3

fault code. Confirm that the

corresponding drive fault relay output is in a faulted state. Drive B will then attempt to start
immediately.

Confirm Drive B starts operating.

END

Содержание H6R B Series

Страница 1: ...YA I H 6 R 0 1 M O D E L S H6RxBxxx Three Phase 480 V 3 to 250 HP A C D R I V E F O R H VA C F A N P U M P A P P L I C AT I O N S R E D U N D A N T D R I V E O P E R AT I O N A L T E S T M A N U A L...

Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIH6R01B HV600 REDUNDANT DRIVE OPERATIONAL TEST MANUAL...

Страница 3: ...mental Safety Information 4 General Safety 4 2 Product Overview 5 How to Read Redundant Drive Catalog Codes 6 Models H6RxBxxx 7 3 Receiving and System Components 7 4 Primary Operation Tests 10 Primary...

Страница 4: ...manual and the standard drive manuals General Safety General Precautions Some figures in the instructions include options and drives without covers or safety shields to more clearly show the inside o...

Страница 5: ...dant Drive Package is engineered for use in critical HVAC building automation applications that require continuous reliable motor control This document provides a procedure to test the operation of th...

Страница 6: ...Drive Catalog Codes Use the information in Figure 2 1 and Table 2 2 to read the catalog codes Figure 2 1 Catalog Code Table 2 2 Catalog Code Details No Description 1 HV600 Redundant Drive 2 Enclosure...

Страница 7: ...3 34 4 180 180 150 240 240 200 Contact Yaskawa 302 302 250 1 Horsepower rating is based on standard NEMA B 4 pole motor design as represented in NEC table 430 150 Full Load Current Three Phase Altern...

Страница 8: ...PLY 24VDC 150 mA MAX P OPTION CARD SHIELD GND FE COMMUNICATIONS INPUT R COMMUNICATIONS INPUT R COMMUNICATIONS OUTPUT S COMMUNICATIONS OUTPUT S JUMPER SH1 to 122 SH1 from 124 RUNNING DRIVE ON POWER FAU...

Страница 9: ...d Current FLA Must be set by user H1 05 6E Terminal Sx Function Selection HAND Command ON HAND Mode OFF OFF Mode or AUTO Mode H1 06 18 Terminal Sx Function Selection Timer Function H1 07 6D Terminal S...

Страница 10: ...10 22 TB1 1SN 138 127 127 to 125 127 from 129 127 128 128 to 125 128 from 129 128 RUNNING DRIVE ON POWER FAULT DRIVE AGREE 1 SPEED RUN FWD S1 RUN REV S2 EXTERNAL FAULT N O S3 FAULT RESET S4 HAND MODE...

Страница 11: ...if necessary set min max speeds and accel decel times etc 11 When commissioning is complete set the HAND OFF AUTO switch to OFF to stop the drive Expanded Function Test Table 4 3 Expanded Function Te...

Страница 12: ...rt Drive A 19 Confirm that you can use the BAS to change the speed reference for Drive A and Drive B 20 If necessary remove the front cover from Drive A to access the TB3 and TB4 terminal blocks below...

Страница 13: ...TIONAL TEST MANUAL 13 Revision History Date of Publication Revision Number Revised Content April 2023 2 Revision Applicable Documents and Catalog Code February 2023 1 Revision Document title Addition...

Страница 14: ...yaskawa eu com www yaskawa eu com YASKAWA EL TRICO DO BRASIL LTDA 777 Avenida Piraporinha Diadema S o Paulo 09950 000 Brasil Phone 55 11 3585 1100 Fax 55 11 3585 1187 www yaskawa com br In the event t...

Отзывы: