SECTION A. 230V
TERMINAL
FUNCTION
1 HP
3 TO 40 HP
L1 (R)
Three phase Main circuit input power supply
L2 (S)
200 / 208 / 220V at 50 Hz; 200 / 208 / 220 / 230V at 60 Hz
L3 (T)
T1 (U)
Three phase AC output to motor
T2 (V)
0V to max. input voltage level
T3 (W)
B1
B2
DB Resistor terminals (B1 & B2)
– – – – – –
⊕
1
DC Reactor terminals (
⊕
1 &
⊕
2)
⊕
2
DC Bus terminals (
⊕
1 &
)
– – – – – –
⊕
3
– – – – – –
DB Unit terminals (
⊕
3 &
)
l
1
(r)
Power for heat sink fan:
l
2
(
s
)
– – – – – –
l
1
to
l
2
: 230 VAC
Ground terminal (100 ohms or less)
SECTION B. 460V
TERMINAL
FUNCTION
1 TO 60 HP
L1 (R)
Three phase Main circuit input power supply
L2 (S)
380 / 400 / 415 / 460V at 50/60 Hz
L3 (T)
T1 (U)
Three phase AC output to motor
T2 (V)
0V to max. input voltage level
T3 (W)
B1
B2
DB Resistor terminals (B1 & B2)
– – – – – –
⊕
1
DC Reactor terminals (
⊕
1 &
⊕
2)
⊕
2
DC Bus terminals (
⊕
1 &
)
– – – – – –
⊕
3
– – – – – –
DB Unit terminals (
⊕
3 &
)
l
1
(r)
Power for heat sink fan:
Power for heat sink fan:
l
2
(
s
)
l
1
to
l
2
: 230 VAC
l
1
to
l
2
200: 230 Vac
l
2
200 (
s
200)
– – – – – –
l
1
to
l
2
400: 460 Vac
l
2
400 (
s
400)
– – – – – –
Ground terminal
SECTION A. 230V
FUNCTION
New Model No.
20P41F -
20111F - 20151F
20181F
20300F - 20750F
TERMINAL
CIMR-G5M
27P51F
20221F
Old Model No.
A003 - A033
A049 - A064
A080, -
A130 - A300
GPD515C-
A096
1-6
Table 1-2. Terminal Functions and Voltages of Main Circuit
– – – – – indicates that terminals are not present.
SECTION B. 460V
FUNCTION
New Model No.
40P41F - 40151F
40181F - 40451F
40551F - 43000F
TERMINAL
CIMR-G5M
Old Model No.
B001 - B034
B041 - B096
B128 - B605
GPD515C-