Fault Codes
Parameter Setting Error
- Inverter can’t run. The fault is displayed
on the digital operator, and the fault relay is not activated.
Closed Loop Flux Vector mode has been selected
without a PG board installed.
OPE06
PG Opt Missing
Possible Cause(s):
PG option board not correctly installed or missing. The control method
selection parameter A1-02 is set to 1 or 3 without a feedback board installed.
Corrective Action:
Verify that an option board is installed. Remove power to the inverter
and connect the option board once more.
OPE07
Analog Selection
The multi-function analog inputs terminals 14 and
16 are set for the same function.
Possible Cause(s):
Duplicate functions are selected.
Corrective Action:
Verify the set values of H3-09 (terminal 14 selection) and H3-05
(terminal 16 selection).