GPD315/V7 Modbus RTU Technical Manual TM 4325
Page
31
Table 5-4 Drive Parameters (continued)
Parameter
ADDR
Name
Set
Description
Default
n159
019Fh
Energy-Saving
Voltage Upper
Limit @60Hz
0 - 120%
120
n160
01A0h
Energy-Saving
Voltage Upper
Limit @6Hz
0 - 25%
16
n161
01A1h
Search Power
Supply Detect
Hold Width
0 - 100%
10
n162
01A2h
Power
Detection Filter
Time Constant
0 - 255
(1 = 4ms)
5
n163
01A3h
PID Output
Gain
0.0 - 25.0
1.0
0
0 – 10v
Terminal Fr
1
4 – 20ma
Terminal FR
2
0 – 20ma
Terminal FR
3
0 – 10v
Operator Terminal
4
4 – 20ma
Operator Terminal
n164
01A4h
PID Feedback
Selection
5
Pulse Input
0
n165-n174
01A5-
01AFh
Reserved
3
0
Disabled
n175
01B0h
Carrier Freq.
Deceleration
@ Low Speed
1
Enabled
@ Output Freq.
≤
5 and Output Current
≤
110%
Carrier Frequency is automatically reduced to 2.5kHz
0
rdy
Ready Status
rEd
Read Executes
CPy
Copy Executes
vFy
Verify Executes
vA
Drive Capacity Display
n176
11
01B1h
Parameter
Copy Function
Sno
Software No. Display
rdy
0
Read Prohibited
n177
11
01B2h
Parameter
Read Prohibit
1
Read Allowed
0
n178
01B3h
Fault History
Four Newest Events Are Displayed.
-
n179
01B4h
Software No.
Lower Four Digits Of Software Numbers Are Displayed.
-
0
Enabled
n180
01B4h
Output Voltage
Limiter
1
Disabled
0
0
Enabled
n181
01B5h
Electronic
Thermal
Inverter
Protection
1
Disabled
0
0
Enabled
n182
01B6h
Simple AVR
Selection
1
Disabled
0
0
Modbus Communication At PC Connection
n183
01B7h
RS485
Terminal
Monitor
1
Modbus Communication (Test Mode) At PC
0
n184
01B8h
Hunting
Prevent Gain
0.00 To 2.55
(V/F Control Mode Only)
6
n185
01B9h
Hunting
Prevent Time
Constant
1 To 255
(1 = 2ms)
6
n186
01BAh
Magnetic Flux
Hunting
Prevent Gain
0.00 To 1.00
(Vector Control Mode Only)
0.05
n187
01BBh
D-Axis Hunting
Prevent Gain
0.00 To 2.55
(Vector Control Mode Only)
6