GPD315/V7 Modbus RTU Technical Manual TM 4325
Page
26
Table 5-4 Drive Parameters (continued)
Parameter
ADDR
Name
Set
Description
Default
0
@ Fault
1
@ Running
2
@ Speed Agree
3
@ Zero Speed
4
Frequency Detection
≤
n095
5
Frequency Detection
≥
n095
6
Overtorque Detection
(N.O. Contact)
7
Overtorque Detection
(N.C. Contact)
8
Reserved
3
9
Reserved
3
10
Minor Fault
11
@ Baseblock
12
@ Run Mode
13
Inverter Ready
14
@ Fault Retry
15
@ Undervoltage
16
@ Reverse
17
@ Speed Search
18
Serial Communications
n057
0132
9h
Multi-Function
Output 1
(MA-MB-MC)
19
@ PID Feedback Loss
1
n058
013Ah
Multi-Function
Output 2
(PHC1-PHCC)
Same As Parameter n057
1
n059
013Bh
Multi-Function
Output 2
(PHC2-PHCC)
Same As Parameter n057
2
n060
013Ch
Analog
Freq. Ref. Gain
0 – 255%
100
n061
013Dh
Analog
Freq. Ref. Bias
±100%
0
n062
013Eh
Analog
Freq. Ref.
Time Constant
0.00 – 2.00 Seconds
(0.00 Disables)
0.10
n063
013Fh
Reserved
3
n064
0140h
Reserved
3
0
Analog Monitor Output
n065
0141h
Monitor Output
1
Pulse Monitor Output
(±12vdc±10%)
(Max. 20mA)
0
0
Output Frequency
(10vdc/Max Output Frequency)
1
Output Current
(10vdc/Drive Rated Current)
2
DC Bus Voltage
(10vdc/400vdc [800vdc])
3
Torque
(10vdc/Drive Rated Torque)
n066
0142h
Monitor Item
4
Output Power
(10vdc/Drive Rated kW)
0
n067
0143h
Monitor Gain
0.01 – 2.00
1.00
n068
0144h
Analog
Freq. Ref. Gain
±255%
(Operator Voltage Input)
100