846
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
■
101 to 19F: Inverse Input of 1 to 9F
Setting Value
Function
Description
101 to 19F
Inverse Inputs of 1 to 9F
Sets the function of the selected MFDI to operate inversely. To select the function, enter
“
1xx
”
, where the
“
xx
”
is the function setting
value.
For example, to use the inverse input of
E [ASR Integral Reset]
, set
H1-xx = 10E
.
Note:
You cannot use inverse input for all functions. Refer to
for more information.
◆
H2: Digital Outputs
H2 parameters
set the MFDO terminal functions.
■
H2-01 to H2-03 Terminal M1-M2, M3-M4, M5-M6 Function Selection
The drive has three MFDO terminals.
shows the default function settings for the terminals.
Table 12.60 MFDO Terminals Default Function Settings
No.
Name
Default
Function
H2-01
Term M1-M2 Function Selection
0
During Run
H2-02
Term M3-M4 Function Selection
1
Zero Speed
H2-03
Term M5-M6 Function Selection
2
Speed Agree 1
Refer to
to set
H2-xx [MFDO Function Selection]
.
Table 12.61 MFDO Setting Value
Setting Value
Function
Reference
0
During Run
1
Zero Speed
2
Speed Agree 1
3
User-Set Speed Agree 1
4
Frequency Detection 1
5
Frequency Detection 2
6
Drive ready
7
DC Bus Undervoltage
8
During Baseblock (N.O.)
9
Frequency Reference from Keypad
A
Run Command from Keypad
B
Torque Detection 1 (N.O.)
C
Frequency Reference Loss
D
Braking Resistor Fault
E
Fault
F
Not Used
10
Alarm
11
Fault Reset Command Active
12
Timer Output
13
Speed Agree 2
14
User-Set Speed Agree 2
15
Frequency Detection 3
16
Frequency Detection 4
Setting Value
Function
Reference
17
Torque Detection 1 (N.C.)
18
Torque Detection 2 (N.O.)
19
Torque Detection 2 (N.C.)
1A
During reverse
1B
During Baseblock (N.C.)
1C
Motor 2 Selected
1D
During Regeneration
1E
Executing Auto-Restart
1F
Motor Overload Alarm (oL1)
20
Drive Overheat Pre-Alarm (oH)
21
Safe Torque OFF
22
Mechanical Weakening Detection
2F
Maintenance Notification
30
During Torque Limit
31
During Speed Limit
32
In Speed Limit During Trq Ctrl
33
Zero Servo Complete
37
During Frequency Output
38
Drive Enabled
39
Watt Hour Pulse Output
3C
LOCAL Control Selected
3D
During Speed Search
3E
PID Feedback Low
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...