E5-11: Encoder Z-Pulse Offset
No.
(Hex.)
Name
Description
Default
(Range)
E5-11
(0333)
Encoder Z-Pulse Offset
Sets the encoder Z-pulse offset.
0.0 degrees
(-180.0 - +180.0 degrees)
The drive uses the PM motor parameter settings and PM Stationary Auto-Tuning to set
E5-11
to the value input for
“
Encoder Z-Pulse Offset
”
automatically. The drive uses Z Pulse Offset Tuning or the Rotational Auto-Tuning to set
E5-11
.
■
E5-24: PM Back-EMF L-L Vrms (mV/rpm)
No.
(Hex.)
Name
Description
Default
(Range)
E5-24
(0353)
PM Back-EMF L-L Vrms
(mV/rpm)
Sets the RMS value for PM motor line voltage.
0.1 mV/min
-1
(0.0 - 6500.0 mV/min
-1
)
Set this parameter when you use an SPM motor (SMRA-Series Pico motor).
PM motor Auto-Tuning automatically sets this parameter to the value of [Back-EMF Voltage Constant (Ke)].
When
E5-01 = FFFF
, only set
E5-09 [PM Back-EMF Vpeak (mV/(rad/s))]
or
E5-24
as the induced voltage constant.
Note:
When you set this parameter, also set
E5-09 = 0.0
. The drive will detect
oPE08 [Parameter Selection Error]
in these conditions:
•
E5-09 = 0.0
and
E5-24 = 0.0
•
E5-09 ≠ 0.0
and
E5-24 ≠ 0.0
■
E5-25: Polarity Estimation Timeout
No.
(Hex.)
Name
Description
Default
(Range)
E5-25
(035E)
Expert
Polarity Estimation Timeout
Sets the function that switches polarity for initial polarity estimation. Usually it is not necessary to
change this setting.
0
(0, 1)
When
“
Sd = 1
”
is shown on the motor nameplate or test report for Yaskawa motors, set this parameter to
1
.
0 : Disabled
1 : Enabled
◆
E9: Motor Setting
E9 parameters
set SynRM motors. Set these parameters to derate torque applications when a high level of
responsiveness and accurate speed control are not necessary. Auto-Tuning the drive will automatically set the
E9
parameters
.
If you cannot do EZ Tuning, you can also manually set the
E9 parameters
.
■
E9-01: Motor Type Selection
No.
(Hex.)
Name
Description
Default
(Range)
E9-01
(11E4)
Motor Type Selection
Sets the type of motor.
0
(0 to 2)
EZ Tuning automatically sets this parameter to the value of [Motor Type Selection].
0 : Induction (IM)
1 : Permanent Magnet (PM)
2 : Synchronous Reluctance (SynRM)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...