3.15 Branch Circuit Protection
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
125
Drive Model
Semiconductor Fuse
Manufacturer: EATON/Bussmann
Alternate Time-Delay
Class CC, J, or T
Maximum Amp Rating
(Maximum SCCR (kA))
2257
FWH-600A
400 (100)
2313
FWH-800A
500 (100)
2360
FWH-1000A
600 (100)
2415
FWH-1000A
800 (100)
*1
Class T fuses are fast-acting (non-time delay only).
*2
Yaskawa recommends a fuse with a larger rated current for cyclical load applications that frequently approach 150 % overload.
*3
For fuses rated 601 - 800 amps, you must use Class T fuses.
■
400 V Class
Table 3.20 Factory Recommended Fuses for 400 V Class
Drive Model
Semiconductor Fuse
Manufacturer: EATON/Bussmann
Alternate Time-Delay
Class CC, J, or T
Maximum Amp Rating
(Maximum SCCR (kA))
4002
FWH-50B
3.5 (100)
4004
FWH-50B
7 (100)
4005
FWH-50B
9 (100)
4007
FWH-60B
12 (100)
4009
FWH-60B
15 (100)
4012
FWH-60B
20 (100)
4018
FWH-80B
30 (100)
4023
FWH-90B
40 (100)
4031
FWH-150B
50 (100)
4038
FWH-200B
60 (100)
4044
FWH-200B
70 (100)
4060
FWH-225A
100 (100)
4075
FWH-250A
125 (100)
4089
FWH-275A
150 (100)
4103
FWH-275A
175 (100)
4140
FWH-300A
225 (100)
4168
FWH-325A
250 (100)
4208
FWH-500A
350 (100)
4250
FWH-600A
400 (100)
4302
FWH-700A
500 (100)
4371
FWH-800A
Not applicable
4414
FWH-1000A
Not applicable
4477
FWH-1200A
Not applicable
4568
FWH-1200A
Not applicable
4605
FWH-1400A
Not applicable
4720
FWH-1400A
Not applicable
*1
Class T fuses are fast-acting (non-time delay only).
*2
Yaskawa recommends a fuse with a larger rated current for cyclical load applications that frequently approach 150 % overload.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...