YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
315
■
E9-07: Motor Rated Power
No.
(Hex.)
Name
Description
Default
(Range)
E9-07
(11EA)
Motor Rated Power
Sets the motor rated power in the units from
o1-58 [Motor Power Unit Selection]
.
Determined by E9-02 and
o2-04
(0.00 - 650.00 HP)
Auto-Tuning automatically sets this parameter to the value of [Motor Rated Power (kW)].
■
E9-08: Motor Pole Count
No.
(Hex.)
Name
Description
Default
(Range)
E9-08
(11EB)
Motor Pole Count
Sets the number of motor poles.
4
(2 to 120)
Auto-Tuning automatically sets this parameter to the value of [Number of Motor Poles].
■
E9-09: Motor Rated Slip
No.
(Hex.)
Name
Description
Default
(Range)
E9-09
(11EC)
Motor Rated Slip
Sets the motor rated slip.
0.000 Hz
(0.000 - 20.000 Hz)
The setting value of this parameter is the slip compensation reference value.
The drive uses the setting values of
E9-03
,
E9-04
, and
E9-08
to calculate this parameter. When Motor Rated Slip = 0,
Auto-Tuning automatically sets this parameter to the value of [Motor Rated Slip].
Note:
Set
E9-01 = 0 [Motor Type Selection = Induction (IM)]
before you set this parameter.
■
E9-10: Motor Line-to-Line Resistance
No.
(Hex.)
Name
Description
Default
(Range)
E9-10
(11ED)
Motor Line-to-Line
Resistance
Sets the line-to-line resistance for the motor stator windings.
Determined by o2-04
(0.000 - 65.000 Ω)
Note:
This value is the motor line-to-line resistance. Do not set this parameter with the single-phase resistance.
Stationary Auto-Tuning automatically sets this parameter. If you cannot do Stationary Auto-Tuning, use the test report
from the motor manufacturer. You can calculate the motor line-to-line resistance with one of these formulas:
•
E-type insulation: the resistance value (Ω) shown on the test report at 75 °C × 0.92
•
B-type insulation: the resistance value (Ω) shown on the test report at 75 °C × 0.92
•
F-type insulation: the resistance value (Ω) shown on the test report at 115 °C × 0.87
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...
Страница 172: ...1 22 Parameters Changed by PM Motor Code Selection 172 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...