2.10 Troubleshooting Without Fault Display
YASKAWA
TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
139
2.10
Troubleshooting Without Fault Display
Note:
Make sure that you use a keypad that has a flash number of 1004 or later. Keypads that have a flash number of 1003 or earlier will not show
characters correctly.
If the drive or motor operate incorrectly, but the keypad does not show a fault or error code, refer to the items this
section.
•
Motor hunting and oscillation
•
Unsatisfactory motor torque
•
Unsatisfactory speed precision
•
Unsatisfactory motor torque and speed response
•
Motor noise
◆
Typical Problems
Symptom
Ref.
The Parameter Settings Will Not Change
The Motor Does Not Rotate after You Enter a Run Command
The Motor Rotates in the Opposite Direction from the Run Command
The Motor Rotates in Only One Direction
The Motor Is Too Hot
The Correct Auto-Tuning Mode Is Not Available
The Motor Stalls during Acceleration or Accel/Decel Time Is Too Long
The Drive Frequency Reference Is Different than the Controller Frequency Reference Command
The Motor Is Not Stable When Using a PM Motor
There Is Too Much Motor Oscillation and the Rotation Is Irregular
Deceleration Takes Longer than Expected when You Enable Dynamic Braking
There Is Audible Noise from the Drive or Motor Cables when You Energize the Drive
The Ground Fault Circuit Interrupter (GFCI) Trips During Run
Motor Rotation Causes Unexpected Audible Noise from Connected Machinery
Motor Rotation Causes Oscillation or Hunting
PID Output Fault
The Starting Torque Is Not Sufficient
The Motor Rotates after You Shut Off Drive Output
The Output Frequency Is Lower Than the Frequency Reference
The Motor Is Making an Audible Noise
The Motor Will Not Restart after Power Loss
◆
The Parameter Settings Will Not Change
Causes
Possible Solutions
The drive is operating the motor (the drive is in Drive Mode).
Stop the drive and change to Programming Mode.
Parameter
A1-01 = 0 [Access Level Selection = Operation Only]
.
Set
A1-01 = 2 [Access Level Selection = Advanced Level]
or
A1-01 = 3 [Expert Level]
.
Parameter
H1-xx = 1B [MFDI Function Select = Programming Lockout]
.
Activate the terminals to which
H1-xx = 1B
is set, and then change the parameters.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 430: ...5 18 Motor Application Precautions 430 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...