2.10 Troubleshooting Without Fault Display
146
YASKAWA
TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
Causes
Possible Solutions
L3-01 = 3 [Stall Prevent Select duringAccel = ILim Mode]
has been set.
1.
Check whether the V/f pattern and motor parameter settings are appropriate, and set them
correctly.
2.
If this does not solve the problem, and it is not necessary to limit the current level of stall during
acceleration, adjust
L3-02
.
3.
If this does not solve the problem, set
L3-01 = 1 [Enabled]
.
The motor is rotating at this speed:
b2-01 [DC Injection/Zero SpeedThreshold]
≤ Motor Speed <
E1-09 [Minimum
Output Frequency]
•
Set
b1-21 = 1 [CLV Start Selection = Accept Run command at any speed].
•
Set
E1-09 < b2-01
.
◆
The Motor Is Making an Audible Noise
Causes
Possible Solutions
100% of the rated output current of the drive was exceeded while operating at
low speeds.
•
If the sound is coming from the motor, set
L8-38 = 0 [Carrier Frequency Reduction = Disabled]
.
•
If
oL2 [Drive Overloaded]
occurs frequently after setting
L8-38 = 0
, replace the drive with a
high-capacity drive.
◆
The Motor Will Not Restart after a Loss of Power
Causes
Possible Solutions
The drive did not receive a Run command after applying power.
•
Examine the sequence and wiring that enters the Run command.
•
Set up a relay to make sure that the Run command stays enabled during a loss of power.
For applications that use 3-wire sequence, the momentary power loss continued
for a long time, and the relay that keeps the Run command has been switched
off.
Examine the wiring and circuitry for the relay that keeps the Run command enabled during the
momentary power loss ride-thru time.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 430: ...5 18 Motor Application Precautions 430 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...