YASKAWA
TOEPC71061779B GA800 Drive Installation Manual
35
4.
Hold the fan finger guard at an angle and put the connector tabs on the fan finger guard into the holes on the
drive.
A - Front of drive
B - Drive holes
C - Tab
Figure 4.12 Reattach the Fan Finger Guard
5.
Push the hook on the back side of the fan finger guard and click it into place on the drive.
Figure 4.13 Reattach the Fan Finger Guard
6.
Energize the drive and set
o4-03 = 0 [Fan Operation Time Setting = 0 h]
to reset the cooling fan operation
time.
■
Replace a Fan (Procedure C)
DANGER
Electrical Shock Hazard. Do not examine, connect, or disconnect wiring on an energized drive. Before servicing,
disconnect all power to the equipment and wait for the time specified on the warning label at a minimum. The internal capacitor
stays charged after the drive is de-energized. The charge indicator LED extinguishes when the DC bus voltage decreases below 50
Vdc. When all indicators are OFF, remove the covers before measuring for dangerous voltages to make sure that the drive is safe. If
you do work on the drive when it is energized, it will cause serious injury or death from electrical shock.
CAUTION
Burn Hazard. Do not touch a hot drive heatsink. De-energize the drive, wait for a minimum of 15 minutes, then
make sure that the heatsink is cool before you replace the cooling fans. If you touch a hot drive heatsink, it can burn you.
NOTICE
Use the instructions in this manual to replace the cooling fans. When you do maintenance on the fans, replace all
the fans to increase product life. If you install the fans incorrectly, it can cause damage to the drive.