YASKAWA
TOEPYAIGA5002A GA500 Programming
77
1.12
n: Special Adjustment
◆
n1: Hunting Prevention
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
n1-01
(0580)
Hunting Prevention
Selection
Sets the function to prevent hunting.
Note:
When you replace a V1000-series drive with a GA500 drive, set
n1-01 = 1 [Hunting
Prevention Selection = Enabled]
.
0 : Disable
1 : Enabled
0
( 0, 1 )
n1-02
(0581)
Expert
Hunting Prevention Gain
Setting
Sets the performance of the hunting prevention function. Usually it is not necessary to
change this parameter.
1.00
(0.00 - 2.50)
n1-03
(0582)
Expert
Hunting Prevention Time
Constant
Sets the primary delay time constant of the hunting prevention function. Usually it is not
necessary to change this parameter.
Determined by o2-04
(0 - 500 ms)
n1-05
(0530)
Expert
Hunting Prevent Gain in
Reverse
Sets the performance of the hunting prevention function. This parameter adjusts Reverse
run. Usually it is not necessary to change this parameter.
0.00
(0.00 - 2.50)
n1-13
(1B59)
Expert
DC Bus Stabilization
Control
Sets the oscillation suppression function for the DC bus voltage.
0 : Disabled
1 : Enabled
0
(0, 1)
n1-14
(1B5A)
Expert
DC Bus Stabilization
Time
Adjusts the responsiveness of the oscillation suppression function for the DC bus voltage.
Set
n1-13 = 1 [DC Bus Stabilization Control = Enabled]
to enable this parameter.
100.0 ms
(50.0 - 500.0 ms)
◆
n2: Auto Freq Regulator (AFR)
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
n2-01
(0584)
Automatic Freq Regulator
Gain
Sets the gain of the AFR function as a magnification value. Usually it is not necessary to
change this setting.
1.00
(0.00 - 10.00)
n2-02
(0585)
Automatic Freq Regulator
Time 1
Sets the time constant that sets the rate of change for the AFR function. Usually it is not
necessary to change this setting.
50 ms
(0 - 2000 ms)
n2-03
(0586)
Automatic Freq Regulator
Time 2
Sets the time constant that sets the speed difference of the AFR function. Use this
parameter for speed searches or regeneration. Usually it is not necessary to change this
setting.
750 ms
(0 - 2000 ms)
◆
n3: High Slip/Overexcite Braking
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
n3-01
(0588)
Expert
HSB Deceleration
Frequency Width
Sets the amount by which the output frequency is to be lowered during high-slip braking,
as a percentage of
E1-04 [Maximum Output Frequency]
, which represents the 100% value.
5%
(1 - 20%)
n3-02
(0589)
Expert
HSB Current Limit Level
Sets the maximum current output during high-slip braking as a percentage, where
E2-01
[Motor Rated Current (FLA)]
is 100%. Also set the current suppression to prevent
exceeding drive overload tolerance.
Note:
The upper limit to the setting range changes when the setting for
C6-01 [Normal /
Heavy Duty Selection]
changes.
•
150% when
C6-01 = 0 [Heavy Duty Rating]
•
120% when
C6-01 = 1 [Normal Duty Rating]
Determined by C6-01
(0 - 150%)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...