34
YASKAWA
TOEPYAIGA5002A GA500 Programming
1.8
E: Motor Parameters
◆
E1: V/f Pattern for Motor 1
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
E1-01
(0300)
Input AC Supply Voltage
Sets the drive input voltage.
NOTICE:
Set parameter E1-01 to align with the drive input
voltage (not motor voltage). If this parameter is incorrect, the
protective functions of the drive will not operate correctly and it
can cause damage to the drive.
200 V Class: 240 V, 400
V: 480 V
(200 V Class: 155 to 255
V, 400 V Class: 310 to
510 V)
E1-03
(0302)
V/f Pattern Selection
Sets the V/f pattern for the drive and motor. You can use one of the preset patterns or you
can make a custom pattern.
0 : Const Trq, 50Hz base, 50Hz max
1 : Const Trq, 60Hz base, 60Hz max
2 : Const Trq, 50Hz base, 60Hz max
3 : Const Trq, 60 Hz base, 72 Hz max
4 : VT, 50Hz, 65% Vmid reduction
5 : VT, 50Hz, 50% Vmid reduction
6 : VT, 60 Hz, 65% Vmid reduction
7 : VT, 60 Hz, 50% Vmid reduction
8 : High Trq, 50Hz, 25% Vmin Boost
9 : High Trq, 50Hz, 65% Vmin Boost
A : High Trq, 60 Hz, 25% Vmin Boost
B : High Trq, 60 Hz, 65% Vmin Boost
C : Const Trq, 60 Hz base, 90 Hz max
D : Const Trq, 60 Hz base, 120 Hz max
E : Const Trq, 60 Hz base, 180 Hz max
F : V/f Pattern Selection
Note:
•
When
A1-02 = 2 [Control Method Selection = OLV]
, settings
0
to
E
are not
available.
•
Set the correct V/f pattern for the application and operation area. An incorrect V/f
pattern can decrease motor torque and increase current from overexcitation.
F
(Determined by A1-02)
E1-04
(0303)
Maximum Output
Frequency
Sets the maximum output frequency for the V/f pattern.
Determined by A1-02 and
E5-01
(Determined by A1-02
and E5-01)
E1-05
(0304)
Maximum Output Voltage
Sets the maximum output voltage for the V/f pattern.
200 V Class: 230.0 V, 400
V: 460.0 V
(200 V Class: 0.0 - 255.0
V, 400 V Class: 0.0 -
510.0 V)
E1-06
(0305)
Base Frequency
Sets the base frequency for the V/f pattern.
Determined by A1-02 and
E5-01
(0.0 - E1-04)
E1-07
(0306)
Mid Point A Frequency
Sets a middle output frequency for the V/f pattern.
Determined by A1-02
(0.0 - E1-04)
E1-08
(0307)
Mid Point A Voltage
Sets a middle output voltage for the V/f pattern.
Determined by A1-02
,
C6-01 and o2-04
(200 V Class: 0.0 - 255.0
V,
400 V Class: 0.0 - 510.0
V)
E1-09
(0308)
Minimum Output
Frequency
Sets the minimum output frequency for the V/f pattern.
Determined by A1-02 and
E5-01
(Determined by A1-02,
E1-04, and E5-01)
E1-10
(0309)
Minimum Output Voltage
Sets the minimum output voltage for the V/f pattern.
Determined by A1-02
(200 V Class: 0.0 to 255.0
V, 400 V Class: 0.0 to
510.0 V)
E1-11
(030A)
Expert
Mid Point B Frequency
Sets a middle output frequency for the V/f pattern.
0.0 Hz
(0.0 - E1-04)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...