YASKAWA
TOEPYAIGA5002A GA500 Programming
249
■
E1-05: Maximum Output Voltage
No.
(Hex.)
Name
Description
Default
(Range)
E1-05
(0304)
Maximum Output Voltage
Sets the maximum output voltage for the V/f pattern.
200 V Class: 230.0 V, 400 V:
460.0 V
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
■
E1-06: Base Frequency
No.
(Hex.)
Name
Description
Default
(Range)
E1-06
(0305)
Base Frequency
Sets the base frequency for the V/f pattern.
Determined by A1-02 and
E5-01
(0.0 - E1-04)
■
E1-07: Mid Point A Frequency
No.
(Hex.)
Name
Description
Default
(Range)
E1-07
(0306)
Mid Point A Frequency
Sets a middle output frequency for the V/f pattern.
Determined by A1-02
(0.0 - E1-04)
■
E1-08: Mid Point A Voltage
No.
(Hex.)
Name
Description
Default
(Range)
E1-08
(0307)
Mid Point A Voltage
Sets a middle output voltage for the V/f pattern.
Determined by A1-02
,
C6-
01 and o2-04
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
Note:
Default setting is determined by
A1-02 [Control Method Selection]
,
C6-01 [Normal / Heavy Duty Selection]
, and
o2-04 [Drive Model
Selection]
.
■
E1-09: Minimum Output Frequency
No.
(Hex.)
Name
Description
Default
(Range)
E1-09
(0308)
Minimum Output Frequency
Sets the minimum output frequency for the V/f pattern.
Determined by A1-02 and
E5-01
(Determined by A1-02, E1-
04, and E5-01)
■
E1-10: Minimum Output Voltage
No.
(Hex.)
Name
Description
Default
(Range)
E1-10
(0309)
Minimum Output Voltage
Sets the minimum output voltage for the V/f pattern.
Determined by A1-02
(200 V Class: 0.0 to 255.0 V,
400 V Class: 0.0 to 510.0 V)
■
E1-11: Mid Point B Frequency
No.
(Hex.)
Name
Description
Default
(Range)
E1-11
(030A)
Expert
Mid Point B Frequency
Sets a middle output frequency for the V/f pattern.
0.0 Hz
(0.0 - E1-04)
Note:
Set this parameter to
0.0
to disable the function.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...