YASKAWA
TOEPYAIGA5002A GA500 Programming
165
2 : Allow Programming Only at Stop
The drive does not let the user enter Programming Mode when the drive is operating. The drive does not show the
Programming Mode when a Run command is active.
■
b1-14: Phase Order Selection
No.
(Hex.)
Name
Description
Default
(Range)
b1-14
(01C3)
Phase Order Selection
Sets the phase order for output terminals U/T1, V/T2, and W/T3. This parameter can align the
Forward Run command from the drive and the forward direction of the motor without changing
wiring.
0
(0, 1)
0 : Standard
1 : Switch Phase Order
■
b1-15: Frequency Reference Selection 2
No.
(Hex.)
Name
Description
Default
(Range)
b1-15
(01C4)
Frequency Reference
Selection 2
Sets the input method for frequency reference 2.
0
(0 - 4)
This parameter is enabled when
H1-xx = 2 [MFDI Function Selection = External Reference 1/2 Selection]
is
activated.
Note:
•
Push
on the keypad to set the input mode to LOCAL and use the keypad to enter the frequency reference.
•
If the frequency reference is 0 Hz or less than or equal to the value set in
E1-09 [Minimum Output Frequency]
and the drive receives the
Run command, the RUN LED on the keypad will flash. Examine the setting for the frequency reference input and enter a value more than
or equal to
E1-09
.
0 : Keypad
Use the keypad to enter the frequency reference.
Use
and
on the keypad to change the frequency reference.
1 : Analog Input
Use MFAI terminals A1 and A2 to input an analog frequency reference with a voltage or current input signal.
•
Voltage Input
Refer to
to use a voltage signal input to one of the MFAI terminals.
Table 2.21 Frequency Reference Voltage Input
Terminal
Terminal Signal
Level
Parameter Settings
Note
Signal Level
Selection
Function Selection
Gain
Bias
A1
0 - 10 V
H3-01 = 0
H3-02 = 0
[Frequency Reference]
H3-03
H3-04
-
-10 - +10 V
H3-01 = 4
A2
0 - 10 V
H3-09 = 0
H3-10 = 0
[Frequency Reference]
H3-11
H3-12
Set DIP switch S1 to
“
V
”
for voltage input.
-10 - +10 V
H3-09 = 4
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...