1.4 A: Initialization Parameters
YASKAWA
TOEPYAIGA5002A GA500 Programming
13
1.4
A: Initialization Parameters
◆
A1: Initialization
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
A1-00
(0100)
RUN
Language Selection
Sets the language for the LCD keypad.
Note:
When you use
A1-03 [Initialize Parameters]
to initialize the drive, the drive will not
reset this parameter.
0 : English
1 : Japanese
2 : German
3 : French
4 : Italian
5 : Spanish
6 : Portuguese
7 : Chinese
8 : Czech
9 : Russian
10 : Turkish
11 : Polish
12 : Greek
0
(0 - 12)
A1-01
(0101)
RUN
Access Level Selection
Sets user access to parameters. The access level controls which parameters the keypad will
display, and which parameters the user can set.
0 : Operation Only
1 : User Parameters
2 : Advanced Level
3 : Expert Level
2
(0 - 3)
A1-02
(0102)
Control Method Selection
Sets the control method for the drive application and the motor.
0 : V/f Control
2 : Open Loop Vector
5 : PM Open Loop Vector
6 : PM Advanced Open Loop Vector
8 : EZ Vector Control
2
(0, 2, 5, 6, 8)
A1-03
(0103)
Initialize Parameters
Sets parameters to default values.
0 : No Initialization
1110 : User Initialization
2220 : 2-Wire Initialization
3330 : 3-Wire Initialization
0
(0 - 3330)
A1-04
(0104)
Password
Entry point for the password set in
A1-05 [Password Setting]
. The user can view the
settings of parameters that are locked without entering the password. Enter the correct
password in this parameter to change parameter settings.
0000
(0000 - 9999)
A1-05
(0105)
Password Setting
Set the password to lock parameters and prevent changes to parameter settings. Enter the
correct password in
A1-04 [Password]
to unlock parameters and accept changes.
0000
(0000 - 9999)
A1-06
(0127)
Application Preset
Sets the drive to operate in selected application conditions.
0 : General-purpose
1 : Water Supply Pump 2
2 : Conveyor
3 : Exhaust Fan
4 : HVAC Fan
5 : Air Compressor
8 : Conveyor 2
0
(0 - 5, 8)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...