2.2 A: Initialization Parameters
YASKAWA
TOEPYAIGA5002A GA500 Programming
143
■
A1-05: Password Setting
No.
(Hex.)
Name
Description
Default
(Range)
A1-05
(0105)
Password Setting
Set the password to lock parameters and prevent changes to parameter settings. Enter the correct
password in
A1-04 [Password]
to unlock parameters and accept changes.
0000
(0000 - 9999)
This parameter can lock these parameter settings:
•
A1-01 [Access Level Selection]
•
A1-02 [Control Method Selection]
•
A1-03 [Initialize Parameters]
•
A1-06 [Application Preset]
•
A1-07 [DriveWorksEZ Function Selection]
•
A2-01 to A2-32 [User Parameter 1 to 32]
Note:
•
Usually, the keypad will not show
A1-05
. To show and set
A1-05
, show
A1-04 [Password]
and then push
and
on the keypad at
the same time.
•
After you set
A1-05
, the keypad will not show it again until you enter the correct password in
A1-04
. Make sure that you remember the
A1-
05
setting value. If you do not know the
A1-05
setting value, contact Yaskawa or your nearest sales representative.
•
When
A1-03 = 2220, 3330 [2-Wire Initialization, 3-Wire Initialization]
, the drive is initialized to
A1-05 = 0000
. Be sure to set the password
again when a password is necessary for the application.
•
Change the setting value in
A1-05
to change the password. The new setting value becomes the new password.
•
When you use the password to unlock and change a parameter, enter a value other than the password in
A1-04
to lock the parameter again
with the same password.
•
If
A1-04
≠
A1-05
, MEMOBUS Communication cannot read or write
A1-05
.
■
A1-06: Application Preset
WARNING!
Sudden Movement Hazard. Check the I/O signals and the external sequences for the drive before you set the
Application Preset function. When you set the Application Preset function (A1-06
≠
0), it changes the I/O terminal functions for the
drive and it can cause equipment to operate unusually. This can cause serious injury or death.
No.
(Hex.)
Name
Description
Default
(Range)
A1-06
(0127)
Application Preset
Sets the drive to operate in selected application conditions.
0
(0 - 5, 8)
The drive software contains the application presets shown below. Set
A1-06
to align with the application to let the
drive automatically set the best parameter settings for the selected application. The drive saves parameters that you
frequently use the application in parameters
A2-01 to A2-16 [User Parameters 1 to 16]
for easy configuration and
reference in Setup Mode.
•
Water supply pump
•
Conveyor
•
Exhaust fan
•
HVAC fan
•
Air compressor
Note:
•
Before you set
A1-06
, make sure that you set
A1-03 = 2220, 3330 [Initialize Parameters = 2-Wire Initialization, 3-Wire Initialization]
to
initialize parameters.
•
It is not possible to change the
A1-06
value. To set an application preset, set
A1-03 = 2220
to initialize parameters, then set this parameter.
If initializing all parameters will cause a problem, do not change the settings.
If you set
A2-33 = 1 [User Parameter Auto Selection = Enabled: Auto Save Recent Parms]
to set parameters to
A2-17 to A2-32 [User
Parameters 17 to 32]
automatically, the drive will reset these parameters when you change the
A1-06
setting.
0 : General-purpose
The drive saves the parameters in
as User Parameters.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...