1.18 Parameters that Change from the Default Settings with A1-02 [Control Method Selection]
108
YASKAWA
TOEPYAIGA5002A GA500 Programming
1.18
Parameters that Change from the Default Settings with
A1-02 [Control Method Selection]
The values for the parameters in these tables depend on the values for parameter
A1-02
. When you change the setting
for
A1-02
, the default settings will change.
Table 1.1 A1-02 = 0, 2 [V/f, OLV]
No.
Name
Range
Unit
Control Method (A1-02 Setting)
V/f
(0)
OLV
(2)
b2-01
DC Injection/Zero
SpeedThreshold
0.0 - 10.0
0.1 Hz
0.5
0.5
b2-04
DC Inject Braking Time at
Stop
0.00 - 10.00
0.01 s
0.50
0.50
b3-01
Speed Search at Start
Selection
0 - 1
1
0
0
b3-02
SpeedSearch Deactivation
Current
0 - 200
1%
120
100
b3-08
Speed Estimation ACR P
Gain
0.00 - 6.00
0.01
0.50
b3-09
Speed Estimation ACR I
Time
0.0 - 1000.0
0.1 ms
2.0
2.0
b3-14
Bi-directional Speed Search
0 - 1
1
0
0
b5-15
PID Sleep Function Start
Level
0.0 - 400.0
0.1 Hz
0.0
0.0
b6-01
Dwell Reference at Start
0.0 - 400.0
0.1 Hz
0.0
0.0
b6-03
Dwell Reference at Stop
0.0 - 400.0
0.1 Hz
0.0
0.0
b8-02
Energy Saving Gain
0.0 - 10.0
0.1
-
0.7
b8-03
Energy Saving Filter Time
0.00 - 10.00
0.01 s
-
0.50
b8-19
E-Save Search Injection
Freq
10 - 300
1 Hz
100
100
C1-11
Accel/Decel Time
Switchover Freq
0.0 - 400.0
0.1 Hz
0.0
0.0
C2-01
S-Curve Time @ Start of
Accel
0.00 - 10.00
0.01 s
0.20
0.20
C3-01
Slip Compensation Gain
0.0 - 2.5
0.1
0.0
1.0
C3-02
Slip Compensation Delay
Time
0 - 10000
1 ms
2000
200
C4-01
Torque Compensation Gain
0.00 - 2.50
0.01
1.00
1.00
C4-02
Torque Compensation
Delay Time
0 - 10000
1 ms
200
20
C5-01
ASR Proportional Gain 1
0.00 - 300.00
0.01
-
-
C5-02
ASR Integral Time 1
0.000 - 60.000
0.001 s
-
-
C5-03
ASR Proportional Gain 2
0.00 - 300.00
0.01
-
-
C5-04
ASR Integral Time 2
0.000 - 10.000
0.001 s
-
-
C5-06
ASR Delay Time
0.000 - 0.500
0.001 s
-
-
C5-07
ASR Gain Switchover
Frequency
0.0 - 400.0
0.1 Hz
0.0Hz
0.0Hz
C6-02
Carrier Frequency Selection
1 - F
1
1
d3-01
Jump Frequency 1
0.0 - 400.0
0.1 Hz
0.0
0.0
d3-02
Jump Frequency 2
0.0 - 400.0
0.1 Hz
0.0
0.0
d3-03
Jump Frequency 3
0.0 - 400.0
0.1 Hz
0.0
0.0
d3-04
Jump Frequency Width
0.0 - 20.0
0.1 Hz
1.0
1.0
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...