2.4 d: Reference Settings
2.4 d: Reference Settings
The figure below gives an overview of the reference input, selections, and priorities.
Figure 2.30
Figure 2.30 Frequency Reference Setting Hierarchy
u
d1: Frequency Reference
n
d1-01 to d1-17: Frequency Reference 1 to 16 and Jog Frequency Reference
The drive lets the user switch up to 17 preset frequency references during run (including the Jog reference) through the
contact inputs. The drive uses the acceleration and deceleration times that have been selected when switching between
each frequency reference.
The Jog frequency overrides all other frequency references and must be selected by a separate contact input.
The multi-step speed references 1, 2, and 3 can be input from analog inputs 1 and 2.
Multi-Step Speed Selection
To use several speed references for a multi-step speed sequence, set the H1-
parameters to 3, 4, 5, and 32 (Multi-Step
Speed Reference 1, 2, 3, and 4). To assign the Jog reference to a contact input, set H1-
to 6.
Notes on using analog inputs as Frequency Reference 1, 2, and 3:
•
Multi-Step Speed 1
Set b1-01 to 1 when setting analog input 1 to Multi-Step Speed 1.
Set b1-01 to 0 when setting d1-01 (Frequency Reference 1) to Multi-Step Speed 1.
•
Multi-Step Speed 2
Set H3-10 (Analog Input 2 Function Selection) to 3 (Auxiliary frequency reference 2 when setting analog input 2) to
Multi-Step Speed 3.
Set H3-10 to 1F (Through mode) when setting d1-03(Frequency Reference 3) to Multi-Step Speed 3.
When inputting 0 to 10 V to analog input 2, set H3-09 to 0.
No.
Name
Setting Range
Default
d1-01 to d1-16
Frequency Reference 1 to 16
<1> The upper limit is determined by the maximum output frequency (E1-04) and upper limit for the frequency reference (d2-01).
0.00 to 120.00 Hz
0.00 Hz
d1-17
Jog Frequency Reference
0.00 to 120.00 Hz
6.00 Hz
H1-
= 2
MEMOBUS comm.
Contact Input
Option Card
Analog Input 1/2
d1-01
(Freq. Ref. 1)
MEMOBUS comm.
Option Card
Analog Input 1/2
d1-01
(Freq. Ref. 1)
b1-01
(Freq. Ref. Selection 1)
b1-15
(Freq. Ref. Selection 2)
Set to supply the
auxiliary frequency reference
Multi-Step Speed
Freq. Ref.
Freq. Ref.
H1-
=6 (Jog Freq. Ref.)
Off when using
an option card
MEMOBUS register 0001h, bit 4
(When 2-wire sequence is selected)
Communication option card
command specifications
Freq. Ref.
4 through 16
Jog Freq. Ref.
d2-03 (Master Speed Ref. Lower Limit)
Remote
Local
=3
=2
=1
=0
=3
=2
=1
=0
NetRef
ComRef
d1-04
d1-15
d1-16
d1-17
0
1
Open
Closed
0
1
0
1
MS 1
Analog Input 2
d1-02
H3-10 = 2
H3-10 = 2
MS 2
MS 4
MS 15
MS 16
Jog Freq. Ref.
LO/RE
common_TMonly
MV1000ParameterGuide_E_conditional.book 140 ページ 2013年10月11日 金曜日 午後8時18分