228
YASKAWA ELECTRIC
TOEP C710687 02B FSDrive-MV1000 Instructions
C.4 MEMOBUS/Modbus Setup Parameters
C.4 MEMOBUS/Modbus Setup Parameters
u
MEMOBUS/Modbus Serial Communication
This section describes parameters necessary to set up MEMOBUS/Modbus communications.
n
H5-01: Drive Node Address
Sets the drive node address used for MEMOBUS/Modbus communications.
Note:
After changing this parameter, the control power must be cycled to enable the new setting.
For serial communications to work, each individual slave drive must be assigned a unique slave address. Setting H5-01
to any value besides 0 assigns the drive its address in the network. Slave address don’t need to be assigned in sequential
order, but each address needs to be unique so that no two drives have the same address.
n
H5-02: Communication Speed Selection
Sets the MEMOBUS/Modbus communications speed.
Note:
After changing this parameter, the control power must be cycled to enable the new setting.
n
H5-03: Communication Parity Selection
Sets the parity used for MEMOBUS/Modbus communications.
Note:
After changing this parameter, the control power must be cycled to enable the new setting.
Setting 0: No parity
Setting 1: Even parity
Setting 2: Odd parity
n
H5-04: Stopping Method after Communication Error (CE)
Selects the stopping method after a communications error (CE) has occurred.
Setting 0: Ramp to stop (uses the deceleration time currently enabled)
Setting 1: Coast to stop
Setting 2: Fast Stop
Setting 3: Alarm only (continue operation)
No.
<1> If the address is set to 0, no response will be provided during communications.
Name
Setting Range
Default
H5-01
Drive Node Address
0 to FF
1F
No.
Name
Setting Range
Default
H5-02
Communication Speed Selection
0 to 5
3
H5-02
Communication Speed
H5-02
Communication Speed
0
1200 bps
5
38400 bps
1
2400 bps
6
57600 bps
2
4800 bps
7
76800 bps
3
9600 bps
8
115200 bps
4
19200 bps
–
–
No.
Name
Setting Range
Default
H5-03
Communication Parity Selection
0 to 2
0
No.
Name
Setting Range
Default
H5-04
Stopping Method after Communication Error (CE)
0 to 3
3
Содержание FSDrive-MV1000 Series
Страница 8: ...8 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 38: ...1 4 Component Names and Configurations 38 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 106: ...3 9 Wiring Check 106 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 136: ...4 9 Checking and Saving Parameter Default Values 136 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 210: ...6 7 Spare Parts 210 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Страница 222: ...B 1 European Standards 222 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...