Figure 11.13 DC Injection Braking Time and Output Frequency
Note:
Set
L2-03
to a high enough value so that
oC [Overcurrent]
is not triggered when using DC Injection Braking to stop the motor.
3 : Coast to Stop with Timer
The drive shuts off its output when the Stop command is entered (or when the Run command is switched OFF).
The motor coasts to stop. The drive ignores the Run command until the
“
Run wait time
”
t has passed.
To start the drive again, re-enter the Run command once the
“
Run wait time
”
t
has passed.
Figure 11.14 Coast to Stop with Timer
The active deceleration time and the output frequency when the Stop command is entered determine the length of
“
Run wait time
”
t
.
Figure 11.15 Run Wait Time and Output Frequency
■
b1-04: Reverse Operation Selection
No.
(Hex.)
Name
Description
Default
(Range)
b1-04
(0183)
Reverse Operation
Selection
Sets the reverse operation function.
0
(0, 1)
The drive does not accept the Reverse operation command when reverse operation is prohibited.
0 : Reverse Enabled
The drive accepts the Reverse operation command.
1 : Reverse Disabled
The drive disregards the Reverse operation command.
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...