b1-02

(0181)

Run Command Selection
1

Sets the input method for the Run command.
0: Keypad, 1: Analog Input, 2: Memobus/Modbus Communications, 3: Option PCB

b1-03

(0182)

Stopping Method
Selection

Sets the method to stop the motor after removing a Run command or entering a Stop
command.
0: Ramp to Stop, 1: Coast to Stop, 2: DC Injection Braking to Stop,
3: Coast to Stop with Timer, 9: Stop with Constant Distance

b1-04

(0183)

Reverse Operation
Selection

Enables and disables reverse operation. Disable reverse operation in fan or pump
applications where reverse rotation is dangerous.
0: Reverse Enabled, 1: Reverse Disabled

C1-01

(0200)

RUN

Acceleration Time 1

Sets the length of time to accelerate from zero to maximum output frequency.

C1-02

(0201)

RUN

Deceleration Time 1

Sets the length of time to decelerate from maximum output frequency to zero.

C2-01

(020B)

S-Curve Time @ Start of
Accel

Sets the time to start S-curve acceleration.

C2-02

(020C)

S-Curve Time @ End of
Accel

Sets the time to complete S-curve acceleration.

C2-03

(020D)

S-Curve Time @ Start of
Decel

Sets the time to start S-curve deceleration.

C2-04

(020E)

S-Curve Time @ End of
Decel

Sets the time to complete S-curve deceleration.

C6-01

(0223)

Normal / Heavy Duty
Selection

Sets the duty rating of the drive.
0: Heavy Duty Rating, 1: Normal Duty Rating

C6-02

(0224)

Carrier Frequency
Selection

Sets the carrier frequency for the transistors in the drive.
1: 2.0 kHz, 2: 5.0 kHz (4.0 kHz for AOLV/PM), 3: 8.0 kHz (6.0 kHz for AOLV/PM),
4: 10.0 kHz (8.0 kHz for AOLV/PM), 5: 12.5 kHz (10.0 kHz for AOLV/PM),
6: 15.0 kHz (12.0 kHz AOLV/PM), 7: Swing PWM 1 (Audible Sound 1),
8: Swing PWM 2 (Audible Sound 2), 9: Swing PWM 3 (Audible Sound 3),
A: Swing PWM 4 (Audible Sound 4), F: User Defined (C6-03 to C6-05)

d1-01 to d1-16

(0280 - 0291)

RUN

Reference 1 to 16

Sets the frequency reference in the units from

o1-03 [Frequency Display Unit Selection]

.

d1-17

(0292)

RUN

Jog Reference

Sets the Jog frequency reference in the units from

o1-03 [Frequency Display Unit

Selection]

. Set

H1-xx = 6 [MFDI Function Select = Jog Reference Selection]

to use the Jog

frequency reference.

d2-01

(0289)

Frequency Reference
Upper Limit

Sets maximum limit for all frequency references. This value is a percentage of

E1-04

[Maximum Output Frequency]

.

d2-02

(028A)

Frequency Reference
Lower Limit

Sets minimum limit for all frequency references. This value is a percentage of

E1-04

[Maximum Output Frequency]

.

E1-01

(0300)

Input AC Supply Voltage

Sets the drive input voltage. Set this parameter to the nominal voltage of the AC power
supply.

E1-04

(0303)

Maximum Output
Frequency

Sets the maximum output frequency for the V/f pattern.

E1-05

(0304)

Maximum Output Voltage Sets the maximum voltage for the V/f pattern.

E1-06

(0305)

Base Frequency

Sets the base frequency for the V/f pattern.

E1-09

(0308)

Minimum Output
Frequency

Sets the minimum output frequency for the V/f pattern.

E2-01

(030E)

Motor Rated Current
(FLA)

Sets the motor rated current in amperes.

EN

Содержание CIPR-GA70C Series

Страница 1: ...Performance Type Initial Steps Type CIPR GA70Cxxxxxxxx Models 200 V class 0 55 to 110 kW 400 V class 0 55 to 355 kW To properly use the product read this manual thoroughly and retain for easy referen...

Страница 2: ...dynamically detect failures and operate safely without exception All products that are designed to incorporate parts manufactured by Yaskawa must be provided to the end user and include proper warning...

Страница 3: ...Tighten screws against the bit at an angle in the specified range described in this manual Tightening screws at an angle outside of the specified range can cause damage the terminal block or start a...

Страница 4: ...specified in this manual DANGER Electrical Shock Hazard Make sure that all electrical connections are correct and install all drive covers before energizing the drive Use terminals for their intended...

Страница 5: ...number in the MODEL section of the drive nameplate to make sure that you received the correct model Contact your supplier if you receive the incorrect drive model or if the drive does not operate cor...

Страница 6: ...ceived a Run command from the MFDI terminals when the drive is not in Drive Mode The drive received a Fast Stop command The safety function shuts off the drive output The user pushed on the keypad whi...

Страница 7: ...ive operation Note Uses a stop priority circuit Push to stop the motor even when a Run command is active at MFDI terminals Set o2 02 0 STOP Key Function Selection Disabled to disable the priority in H...

Страница 8: ...6 Keypad EN 8 YASKAWA ELECTRIC TOEP C710617 17D YASKAWA AC Drive GA700 Initial Steps Keypad Mode and Menu Displays Figure 6 2 Keypad Functions and Display Levels...

Страница 9: ...an external source while in Programming Mode Set b1 08 0 Disregard RUN while Programming to reject the Run command from an external source while in Programming Mode default Set b1 08 1 Accept RUN whil...

Страница 10: ...erate such as when in Programming Mode or when is flashing C RUN Illuminated The drive is in regular operation Flashing 1 The drive is decelerating to stop The drive received a Run command with a freq...

Страница 11: ...ically set these functions Control method selection Duty rating selection Monitor parameters Speed reference source Run command source Acceleration and deceleration times 5 Run the motor without a loa...

Страница 12: ...rect operation and damage to electrical devices Installation Position and Distance Install the drive vertically for sufficient cooling airflow Note Contact Yaskawa or a Yaskawa representative for more...

Страница 13: ...environment is crucial to ensure proper performance and the expected lifespan of the product Ensure the installation environment satisfies the following specifications Environment Conditions Area of U...

Страница 14: ...ear the drive Failure to obey can cause incorrect operation NOTICE Do not let unwanted objects for example metal shavings or wire clippings fall into the drive during drive installation and project co...

Страница 15: ...Keypad connector B Hook C Connector holder Figure 9 5 Remove the Front Cover 6 Remove the wiring cover before wiring the main circuit terminal A Wiring cover Remove the Terminal Cover 1 Loosen the scr...

Страница 16: ...before operating the drive Reattach the Front Cover 1 Reattach the wiring cover 2 Reattach the front cover to the drive with the supplied screws 3 Remove the keypad connector from the connector holder...

Страница 17: ...not maintain the IP20 protective level Hold the cutaway section of the wiring cover firmly to prevent scattering when clipping this section There is a risk of injury from scattering of the cutaway sec...

Страница 18: ...Incorrect Run Stop circuit sequence settings can cause death or serious injury from moving equipment WARNING Sudden Movement Hazard Correctly wire the start stop and safety circuits before energizing...

Страница 19: ...ergize the drive with the fault relay output Set L5 02 1 Fault Contact at Restart Select Always Active to de energize the drive when the drive outputs a fault during fault restart when using the fault...

Страница 20: ...o jumper necessary between terminals SC and SN or terminals SC and SP 12 The maximum output current capacity for terminals Vand Von the control circuit is 20 mA NOTICE Do not install a jumper between...

Страница 21: ...hat users must wire the power supply to automatically turn off when the protective ground wire disconnects Users can also connect a protective ground wire that has a minimum cross sectional area of 10...

Страница 22: ...quipment A Terminal block TB2 3 B Terminal block TB2 2 C Terminal block TB2 1 D DC bus voltage terminals configuration changes by drive model E Drive ground terminals F Motor case ground G Three phase...

Страница 23: ...F ambient temperature 3 Select Setup Wizard and follow the instructions shown on the keypad until the setup wizard completes The drive and motor are prepared for operation Auto Tuning WARNING Crush H...

Страница 24: ...test report data is not available YES Stationary Line Line Resistance 2 Select this tuning mode when The drive and motor capacities are different The drive is in V f Control Replacing the drive and m...

Страница 25: ...een the minimum value and maximum value 8 Push to keep the changes 9 Continue to set parameters or push Back to go back to the HOME screen 12 Drive Control Duty Modes and Programming Drive Control Met...

Страница 26: ...460 V 0 Extruder Conveyor Constant torque or high overload capacity 2 kHz 150 rated output current for 60 s Heavy Duty Rating 2 HD2 460 Vand 480 V Normal Duty Rating 1 ND1 200 Vand 240 V 380 Vand 460...

Страница 27: ...y Rating C6 02 0224 Carrier Frequency Selection Sets the carrier frequency for the transistors in the drive 1 2 0 kHz 2 5 0 kHz 4 0 kHz for AOLV PM 3 8 0 kHz 6 0 kHz for AOLV PM 4 10 0 kHz 8 0 kHz for...

Страница 28: ...A3 Function Selection Sets the function for MFAI terminal A3 H3 07 0415 RUN Terminal A3 Gain Setting Sets the gain of the analog signal input to MFAI terminal A3 H3 08 0416 RUN Terminal A3 Bias Settin...

Страница 29: ...ange this setting L3 04 0492 Stall Prevention during Decel Sets the method that the drive will use to prevent overvoltage faults when decelerating 0 Disabled 1 General Purpose 2 Intelligent Ignore Dec...

Страница 30: ...ect oL1 Motor Overload The motor load is too heavy Decrease the motor load Operating a general purpose motor slower than the rated speed with a high load Use a motor with external cooling and set the...

Страница 31: ...1 PL e Cat III and IEC EN 61508 SIL3 connect a jumper between terminals HC H1 and H2 SToF Safe Torque OFF Hardware Opening only one Safe Disable input disables drive output Usually inputs H1 and H2 m...

Страница 32: ...are subject to change without notice for ongoing product modifications and improvements 2016 YASKAWA Electric Corporation MANUAL NO TOEP C710617 17D 3 0 Published in Japan December 2016 15 11 8_YEU Or...

Отзывы: