12 Drive Control, Duty Modes, and Programming
EN 26
YASKAWA ELECTRIC
TOEP C710617 17D YASKAWA AC Drive GA700 Initial Steps
Control Method
A1-02 Setting
Main Applications
V/f
0
(default)
•
General variable-speed
•
Operating more than one motor from one drive
•
When replacing the motor without motor parameter values.
OLV
2
•
General variable-speed
•
High precision and speed control without speed feedback
EZOLV
8
•
General variable-speed
•
No high precision, no speed control, and no speed feedback
◆
Drive Duty Modes
The drive has two duty modes from which to select for the application: Heavy Duty (HD) and Normal Duty (ND).
The duty rating switches to HD2 or ND2 when
E1-01 [Input AC Supply Voltage]
≥ 460 V. These specifications are
different between HD1/HD2 and ND1/ND2:
•
The input power kVA
•
The maximum applicable motor output
•
The rated input current
•
The rated output capacity
•
The rated output current
Refer to
for information about the differences between HD and ND ratings.
Table 12.1 Drive Duty Modes
Duty Rating
E1-01 Setting
Input Voltage
C6-01
Setting
Application
Default Carrier
Frequency
Overload Tolerance
(oL2 [Drive
Overload])
Heavy Duty Rating 1
(HD1)
•
≥ 200 V and < 240 V
•
≥ 380 V and < 460 V
0
•
Extruder
•
Conveyor
•
Constant torque or high
overload capacity
2 kHz
150% rated output
current for 60 s
Heavy Duty Rating 2
(HD2)
≥ 460 V and < 480 V
Normal Duty Rating
1
(ND1)
•
≥ 200 V and < 240 V
•
≥ 380 V and < 460 V
1
•
Fan
•
Pump
•
Blower
•
Variable speed control
2 kHz Swing-PWM
110% rated output
current for 60 s
Normal Duty Rating
2
(ND2)
≥ 460 V and < 480 V
◆
Drive Parameters
Refer to the following table when setting the most important parameters.
Note:
Users can change parameters with
“
RUN
”
in the
“
No.
”
column during Run.
No.
(Hex.)
Name
Description
A1-00
(0100)
RUN
Language Selection
Sets the language for the LCD keypad.
0: English, 1: Japanese, 2: German, 3: French, 4: Italian, 5: Spanish, 6: Portuguese,
7: Chinese, 8: Czech, 9: Russian, 10: Turkish, 11: Polish, 12: Greek
A1-02
(0102)
Control Method Selection Sets the control method for the drive application and the motor.
0: V/f Control, 1: V/f Control w/ PG, 2: Open Loop Vector, 3: Closed Loop Vector,
4: Advanced Open Loop Vector, 5: PM Open Loop Vector,
6: PM Advanced Open Loop Vector, 7: PM Closed Loop Vector, 8: EZ Vector Control
A1-03
(0103)
Initialize Parameters
Sets parameters to default values.
0: No Initialization, 1110: User Initialization, 2220: 2-Wire Initialization,
3330: 3-Wire Initialization
b1-01
(0180)
Frequency Reference
Selection 1
Sets the input method for the frequency reference.
0: Keypad, 1: Analog Input, 2: Memobus/Modbus Communications, 3: Option PCB,
4: Pulse Train Input