background image

12 Drive Control, Duty Modes, and Programming

EN 26

YASKAWA ELECTRIC

TOEP C710617 17D YASKAWA AC Drive GA700 Initial Steps

Control Method

A1-02 Setting

Main Applications

V/f

0

(default)

General variable-speed

Operating more than one motor from one drive

When replacing the motor without motor parameter values.

OLV

2

General variable-speed

High precision and speed control without speed feedback

EZOLV

8

General variable-speed

No high precision, no speed control, and no speed feedback

Drive Duty Modes

The drive has two duty modes from which to select for the application: Heavy Duty (HD) and Normal Duty (ND).

The duty rating switches to HD2 or ND2 when

E1-01 [Input AC Supply Voltage]

≥ 460 V. These specifications are

different between HD1/HD2 and ND1/ND2:

The input power kVA

The maximum applicable motor output

The rated input current

The rated output capacity

The rated output current

Refer to

Table 12.1

for information about the differences between HD and ND ratings.

Table 12.1 Drive Duty Modes

Duty Rating

E1-01 Setting

Input Voltage

C6-01

Setting

Application

Default Carrier

Frequency

Overload Tolerance

(oL2 [Drive

Overload])

Heavy Duty Rating 1

(HD1)

≥ 200 V and < 240 V

≥ 380 V and < 460 V

0

Extruder

Conveyor

Constant torque or high
overload capacity

2 kHz

150% rated output
current for 60 s

Heavy Duty Rating 2

(HD2)

≥ 460 V and < 480 V

Normal Duty Rating

1

(ND1)

≥ 200 V and < 240 V

≥ 380 V and < 460 V

1

Fan

Pump

Blower

Variable speed control

2 kHz Swing-PWM

110% rated output
current for 60 s

Normal Duty Rating

2

(ND2)

≥ 460 V and < 480 V

Drive Parameters

Refer to the following table when setting the most important parameters.

Note:

Users can change parameters with

RUN

in the

No.

column during Run.

No.

(Hex.)

Name

Description

A1-00

(0100)

RUN

Language Selection

Sets the language for the LCD keypad.
0: English, 1: Japanese, 2: German, 3: French, 4: Italian, 5: Spanish, 6: Portuguese,
7: Chinese, 8: Czech, 9: Russian, 10: Turkish, 11: Polish, 12: Greek

A1-02

(0102)

Control Method Selection Sets the control method for the drive application and the motor.

0: V/f Control, 1: V/f Control w/ PG, 2: Open Loop Vector, 3: Closed Loop Vector,
4: Advanced Open Loop Vector, 5: PM Open Loop Vector,
6: PM Advanced Open Loop Vector, 7: PM Closed Loop Vector, 8: EZ Vector Control

A1-03

(0103)

Initialize Parameters

Sets parameters to default values.
0: No Initialization, 1110: User Initialization, 2220: 2-Wire Initialization,
3330: 3-Wire Initialization

b1-01

(0180)

Frequency Reference
Selection 1

Sets the input method for the frequency reference.
0: Keypad, 1: Analog Input, 2: Memobus/Modbus Communications, 3: Option PCB,
4: Pulse Train Input

Содержание CIPR-GA70C Series

Страница 1: ...Performance Type Initial Steps Type CIPR GA70Cxxxxxxxx Models 200 V class 0 55 to 110 kW 400 V class 0 55 to 355 kW To properly use the product read this manual thoroughly and retain for easy referen...

Страница 2: ...dynamically detect failures and operate safely without exception All products that are designed to incorporate parts manufactured by Yaskawa must be provided to the end user and include proper warning...

Страница 3: ...Tighten screws against the bit at an angle in the specified range described in this manual Tightening screws at an angle outside of the specified range can cause damage the terminal block or start a...

Страница 4: ...specified in this manual DANGER Electrical Shock Hazard Make sure that all electrical connections are correct and install all drive covers before energizing the drive Use terminals for their intended...

Страница 5: ...number in the MODEL section of the drive nameplate to make sure that you received the correct model Contact your supplier if you receive the incorrect drive model or if the drive does not operate cor...

Страница 6: ...ceived a Run command from the MFDI terminals when the drive is not in Drive Mode The drive received a Fast Stop command The safety function shuts off the drive output The user pushed on the keypad whi...

Страница 7: ...ive operation Note Uses a stop priority circuit Push to stop the motor even when a Run command is active at MFDI terminals Set o2 02 0 STOP Key Function Selection Disabled to disable the priority in H...

Страница 8: ...6 Keypad EN 8 YASKAWA ELECTRIC TOEP C710617 17D YASKAWA AC Drive GA700 Initial Steps Keypad Mode and Menu Displays Figure 6 2 Keypad Functions and Display Levels...

Страница 9: ...an external source while in Programming Mode Set b1 08 0 Disregard RUN while Programming to reject the Run command from an external source while in Programming Mode default Set b1 08 1 Accept RUN whil...

Страница 10: ...erate such as when in Programming Mode or when is flashing C RUN Illuminated The drive is in regular operation Flashing 1 The drive is decelerating to stop The drive received a Run command with a freq...

Страница 11: ...ically set these functions Control method selection Duty rating selection Monitor parameters Speed reference source Run command source Acceleration and deceleration times 5 Run the motor without a loa...

Страница 12: ...rect operation and damage to electrical devices Installation Position and Distance Install the drive vertically for sufficient cooling airflow Note Contact Yaskawa or a Yaskawa representative for more...

Страница 13: ...environment is crucial to ensure proper performance and the expected lifespan of the product Ensure the installation environment satisfies the following specifications Environment Conditions Area of U...

Страница 14: ...ear the drive Failure to obey can cause incorrect operation NOTICE Do not let unwanted objects for example metal shavings or wire clippings fall into the drive during drive installation and project co...

Страница 15: ...Keypad connector B Hook C Connector holder Figure 9 5 Remove the Front Cover 6 Remove the wiring cover before wiring the main circuit terminal A Wiring cover Remove the Terminal Cover 1 Loosen the scr...

Страница 16: ...before operating the drive Reattach the Front Cover 1 Reattach the wiring cover 2 Reattach the front cover to the drive with the supplied screws 3 Remove the keypad connector from the connector holder...

Страница 17: ...not maintain the IP20 protective level Hold the cutaway section of the wiring cover firmly to prevent scattering when clipping this section There is a risk of injury from scattering of the cutaway sec...

Страница 18: ...Incorrect Run Stop circuit sequence settings can cause death or serious injury from moving equipment WARNING Sudden Movement Hazard Correctly wire the start stop and safety circuits before energizing...

Страница 19: ...ergize the drive with the fault relay output Set L5 02 1 Fault Contact at Restart Select Always Active to de energize the drive when the drive outputs a fault during fault restart when using the fault...

Страница 20: ...o jumper necessary between terminals SC and SN or terminals SC and SP 12 The maximum output current capacity for terminals Vand Von the control circuit is 20 mA NOTICE Do not install a jumper between...

Страница 21: ...hat users must wire the power supply to automatically turn off when the protective ground wire disconnects Users can also connect a protective ground wire that has a minimum cross sectional area of 10...

Страница 22: ...quipment A Terminal block TB2 3 B Terminal block TB2 2 C Terminal block TB2 1 D DC bus voltage terminals configuration changes by drive model E Drive ground terminals F Motor case ground G Three phase...

Страница 23: ...F ambient temperature 3 Select Setup Wizard and follow the instructions shown on the keypad until the setup wizard completes The drive and motor are prepared for operation Auto Tuning WARNING Crush H...

Страница 24: ...test report data is not available YES Stationary Line Line Resistance 2 Select this tuning mode when The drive and motor capacities are different The drive is in V f Control Replacing the drive and m...

Страница 25: ...een the minimum value and maximum value 8 Push to keep the changes 9 Continue to set parameters or push Back to go back to the HOME screen 12 Drive Control Duty Modes and Programming Drive Control Met...

Страница 26: ...460 V 0 Extruder Conveyor Constant torque or high overload capacity 2 kHz 150 rated output current for 60 s Heavy Duty Rating 2 HD2 460 Vand 480 V Normal Duty Rating 1 ND1 200 Vand 240 V 380 Vand 460...

Страница 27: ...y Rating C6 02 0224 Carrier Frequency Selection Sets the carrier frequency for the transistors in the drive 1 2 0 kHz 2 5 0 kHz 4 0 kHz for AOLV PM 3 8 0 kHz 6 0 kHz for AOLV PM 4 10 0 kHz 8 0 kHz for...

Страница 28: ...A3 Function Selection Sets the function for MFAI terminal A3 H3 07 0415 RUN Terminal A3 Gain Setting Sets the gain of the analog signal input to MFAI terminal A3 H3 08 0416 RUN Terminal A3 Bias Settin...

Страница 29: ...ange this setting L3 04 0492 Stall Prevention during Decel Sets the method that the drive will use to prevent overvoltage faults when decelerating 0 Disabled 1 General Purpose 2 Intelligent Ignore Dec...

Страница 30: ...ect oL1 Motor Overload The motor load is too heavy Decrease the motor load Operating a general purpose motor slower than the rated speed with a high load Use a motor with external cooling and set the...

Страница 31: ...1 PL e Cat III and IEC EN 61508 SIL3 connect a jumper between terminals HC H1 and H2 SToF Safe Torque OFF Hardware Opening only one Safe Disable input disables drive output Usually inputs H1 and H2 m...

Страница 32: ...are subject to change without notice for ongoing product modifications and improvements 2016 YASKAWA Electric Corporation MANUAL NO TOEP C710617 17D 3 0 Published in Japan December 2016 15 11 8_YEU Or...

Отзывы: