Output Terminals
Refer to
and
for a list of Output terminals and functions.
Table 10.5 Control Circuit Output Terminals
Type
Terminal
Name (Default)
Function (Signal Level)
Digital Outputs
MA
N.O. output
(Fault)
•
Relay output
•
30 Vdc, 10 mA to 1 A
•
250 Vac, 10 mA to 1 A
•
Minimum load: 5 V, 10 mA (Reference value)
MB
N.C. output
(Fault)
MC
Digital output common
Multi-function
Photocoupler
Outputs
P1
Multi-function
photocoupler output 1
(During RUN)
•
Photocoupler output
•
48 V, 2 mA to 50 mA
C1
P2
Multi-function
photocoupler output 2
(Speed agree 1)
C2
Table 10.6 Control Circuit Monitor Output Terminals
Type
Terminal
Name (Default)
Function (Signal Level)
Monitor Output
MP
Pulse train output
(Output frequency)
32 kHz (maximum)
Refer to
“
Pulse Train Output
”
(page
) for more
information.
AM
Analog monitor output
(Output frequency)
Select voltage or current output.
•
0 V to 10 V/0% to 100%
•
4 mA to 20 mA (Receiver recommended
impedance: 250 Ω)
Note:
Use jumper S5 and
H4-07 [Terminal AM
Signal Level Select]
to set the signal type.
AC
Monitor common
0 V