44
YASKAWA
SIEP C730600 83E CC-Link Technical Manual
■
Drive Monitor Codes
Table 10.3 Drive Monitor Codes List
Monitor Code (Hex.)
Name
Comments
0000
Reserved
-
0001
Output Frequency
Units are 0.01 Hz, determined by
o1-03 [Frequency Display Unit Selection]
.
0002
Output Current
Units are either 0.1 A or 0.01 A, depending on the capacity of the drive.
0003
Output Voltage Reference
Unit: 0.1 V
0004
Reserved
-
0005
Frequency Reference
Units are 0.01 Hz, determined by
o1-03 [Frequency Display Unit Selection]
.
0006
Motor Speed
Unit: 1 min
-1
0007
Motor Torque
Unit: 0.1%
0008
DC Bus Voltage
Unit: 1 V
0009 - 000D
Reserved
-
000E
Output Power
Unit: 1 V
000F
Input Terminal Status
0010
Output Terminal Status
•
When using 1000-Series
•
When using GA500
•
When using GA700 and GA800
0011
Reserved
-
0012
Motor Excitation Current
Unit: 0.1%
0013
Reserved
-
0014
Cumulative Operation Time
•
Unit: 1 hour
•
Parameter
o4-02 [Elapsed Operating Time Selection]
determines if the operation
time is whenever the drive is powered on or only when there is voltage output.
0015, 0016
Reserved
-
0017
Actual Operation Time
•
Unit: 1 hour
•
Parameter
o4-02 [Elapsed Operating Time Selection]
determines if the operation
time is whenever the drive is powered on or only when there is voltage output.
0018
Motor Secondary Current
-
0019
Cumulative Power
Unit: 1 kW
0034
PID Setpoint Value
Unit: 0.1%
0035
PID Input
Unit: 0.1%
0036
PID Output
Unit: 0.1%