20
YASKAWA
SIEP C730600 83E CC-Link Technical Manual
A - Keypad connector tab
B - Keypad connector
C - Drive front cover
D - Keypad
E - LED Status Ring board
Figure 5.14 Install the LED Status Ring board, Front Cover, and Keypad
7.
Set drive parameters in
Related Drive Parameters on page 23
for correct option performance.
◆
Communication Cable Specifications
Use only CC-Link dedicated communication cable. The Yaskawa warranty does not cover other cable types. For
more information on cables, refer to the CC-Link website at http://www.cc-link.org/.
Yaskawa recommends using CC-Link cables suitable for the conditions listed in the following table.
Table 5.2 Communication Cable Requirements
Item
Specifications
Cable Type
triple-core shielded twisted-pair cable
External Diameter
8.0 mm maximum
Drain Wire
20 lines/0.18 mm or 24 lines/0.18 mm
Electrical
Characteristics
Conductor Resistance (20°C (68°F))
37.8 Ω/km
Insulation Resistance
10000 MΩ
・
km or greater
Voltage Tolerance
500 Vdc, 60 s
Capacitance (1 kHz)
60 nF/km maximum
Impedance
1 MHz
110 ±15 Ω
5 MHz
110 ±6 Ω
Attenuation (20°C (68°
F))
1 MHz
1.6 dB/100 m maximum
5 MHz
3.5 dB/100 m maximum
A - Sheath
B - Shield
C - Aluminum tape
D - DG (yellow)
E - Ground
F - Drain (solid/non-stranded)
G - DB (white)
H - DA (blue)
I - Drain (stranded wire)
Figure 5.15 CC-Link Cable Diagram