TOBP C730600 79C YASKAWA AC Drive Option AO-A3 Installation Manual
6 Related Parameters
6
Related Parameters
The parameters outlined in the following sections are used to set up the drive for operation
with the option. Set parameters as needed. Refer to the manual packaged with the drive for
details on setting parameters.
u
Parameter Table
“RUN” indicates that parameter can be changed during run.
Table 6 Related Parameters
No.
(Addr.
Hex)
Name
Description
Values
F4-01
(391)
Terminal V1 Monitor Selection
Sets the monitor signal for output from
terminal V1.
Default when installed
to drive: 102 (output
frequency)
Default when installed
to energy-saving unit:
000 (reserved)
Range: 000 to 999
F4-02
(392)
RUN
Terminal V1 Monitor Gain
Sets the gain for voltage output via terminal
V1, where 100% equals 10 V output.
Default: 100.0%
Min: -999.9
Max: 999.9
F4-03
(393)
Terminal V2 Monitor Selection
Sets the monitor signal for output from
terminal V2.
Default when installed
to drive: 103 (output
voltage)
Default when installed
to energy-saving unit:
000 (reserved)
Range: 000 to 999
F4-04
(394)
RUN
Terminal V2 Monitor Gain
Sets the gain for voltage output via terminal
V2, where 100% equals 10 V output. Terminal
output voltage is limited to 10 V.
Default: 50.0%
Min: -999.9
Max: 999.9
F4-05
(395)
RUN
Terminal V1 Monitor Bias
Sets the amount of bias added to the voltage
output via terminal V1.
Default: 0.0%
Min: -999.9
Max: 999.9
F4-06
(396)
Terminal V2 Monitor Bias
Sets the amount of bias added to the voltage
output via terminal V2.
Default: 0.0%
Min: -999.9
Max: 999.9
F4-07
(397)
Terminal V1 Signal Level Select
Sets the voltage level for the analog output.
0: 0 V to 10 V
1: -10 V to 10 V
Default: 0
Range: 0, 1
F4-08
(398)
Terminal V2 Signal Level Select
Default: 0
Range: 0, 1