u
U: Monitors
Monitor parameters allow the user to view drive status, fault information, and other information about drive operation.
No.
Name
Description
Analog Output
Level
Unit
Control
Mode
Addr.
Hex
V/
f
O
L
V
P
M
U1: Operation Status Monitors
Use U1 monitors to display the operation status of the drive.
U1-01
Frequency Reference
Monitors the frequency
10 V: Max
frequency
0.01
Hz
A A A
40
U1-02
Output Frequency
Displays the output frequency. Display units are determined
by o1-03.
10 V: Max
frequency
0.01
Hz
A A A
41
U1-03
Output Current
Displays the output current.
10 V: Drive rated
current
0.01
A
<1>
<2>
A A A
42
U1-04
Control Mode
Control method set in A1-02.
0: V/f without PG
2: Open Loop Vector (OLV)
5: PM Open Loop Vector (PM)
No output signal
available
–
A A A
43
U1-05
Motor Speed
Displays the motor speed feedback. Display units are
determined by o1-03.
10 V: Maximum
speed
0.01
Hz
– A –
44
U1-06
Output Voltage Reference
Displays the output voltage.
10 V: 200 Vrms
(400 Vrms)
0.1 V A A A
45
U1-07
DC Bus Voltage
Displays the DC bus voltage.
10 V: 400 V (800
V)
1 V
A A A
46
U1-08
Output Power
Displays the output power (this value is determined
internally).
10 V: Drive
capacity (kW)
(rated motor
capacity)
<1>
A A A
47
U1-09
Torque Reference
Monitor of internal torque reference value for Open Loop
Vector (OLV) control
10 V: Motor rated
torque
–
– A –
48
U1-10
Input Terminal Status
Displays the input terminal status.
Digital input terminal
S1 enabled
Digital input terminal
S2 enabled
Digital input terminal
S3 enabled
Digital input terminal
S4 enabled
Digital input terminal
S5 enabled
Digital input terminal
S6 enabled
Digital input terminal
S7 enabled
No output signal
available
–
A A A
49
B.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
399
B
Parameter List