E: Motor Parameters
No.
Name
Description
Range
Def.
Control
Mode
Addr. Hex Pg.
V/f O
LV PM
E1: V/f Pattern Characteristics
Use E1 parameters to set V/f characteristics for the motor.
E1-01
<1>
Input Voltage
Setting
This parameter must be set to the power supply voltage. It
sets the maximum and base voltage used by preset V/f
patterns (E1-03 = 0 to E) and adjusts levels used by certain
functions.
WARNING! Electrical Shock Hazard. Drive input voltage
(not motor voltage) must be set in E1-01 for the protective
features of the drive to function properly. failure to do so may
result in equipment damage and/or death or personal injury.
155 to 255
230 V
S
S
S
300
E1-03
<2>
V/f Pattern
Selection
Selects a preset V/f pattern.
0: 50 Hz Constant torque 1
1: 60 Hz Constant torque 2
2: 60 Hz Constant torque 3 (50 Hz base)
3: 72 Hz Constant torque 4 (60 Hz base)
4: 50 Hz Variable torque 1
5: 50 Hz Variable torque 2
6: 60 Hz Variable torque 3
7: 60 Hz Variable torque 4
8: 50 Hz High starting torque 1
9: 50 Hz High starting torque 2
A: 60 Hz High starting torque 3
B: 60 Hz High starting torque 4
C: 90 Hz (60 Hz base)
D: 120 Hz (60 Hz base)
E: 180 Hz (60 Hz base)
F: Custom V/f. E1-04 through E1-13 settings define the
V/f pattern
0 to F
F
A
A
−
302
E1-04
Maximum Output
Frequency
E1-04 and E1-06 to E1-13 can only be changed when E1-03
is set to F. To set linear V/f characteristics, set the same
values for E1-07 and E1-09. In this case, the setting for E1-08
will be disregarded.
When E1-13 = 0.0 V, then the drive uses the value set to
E1-05 to control the voltage level.
Ensure that the five frequencies are set according to these
rules to prevent triggering an oPE10 fault:
E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
Note:
Setting E1-11 to 0 disables both E1-11 and E1-12, and
the above conditions do not apply.
E1-09 E1-07 E1-06 E1-11 E1-04
E1-05
E1-12
E1-13
E1-08
E1-10
VACrms Out(V)
Frequency (Hz)
40.0 to
400.0
<3>
60 Hz
<4>
S
S
S
303
E1-05
<1>
Maximum Output
Voltage
0.0 to 255.0
230 V
<4>
S
S
S
304
E1-06
Base Frequency
0.0 to
E1-04
60 Hz
<4>
S
S
S
305
E1-07
Middle Output
Frequency
0.0 to
E1-04
3.0 Hz
<3>
A
A
-
306
E1-08
<1>
Middle Output
Frequency Voltage
0.0 to 255.0
18.4 V
<5>
<6>
A
A
-
307
E1-09
Minimum Output
Frequency
0.0 to
E1-04
1.5 Hz
<5>
<4>
S
S
S
308
E1-10
<1>
Minimum Output
Frequency Voltage
0.0 to 255.0
13.8 V
<5> <6>
A
A
-
309
E1-11
Middle Output
Frequency 2
0.0 to
E1-04
0.0 Hz
A
A
-
30A
E1-12
<1>
<7>
Middle Output
Frequency Voltage
2
0.0 to 255.0
0.0 V
A
A
-
30B
E1-13
<1>
<9>
Base Voltage
0.0 to 255.0
0.0 V
A
S
-
30C
E2: Motor Parameters
Use E2 parameters to set motor-related data.
E2-01
<8>
Motor Rated
Current
Sets the motor nameplate full load current in amperes (A).
Automatically set during Auto-Tuning.
Note:
Set E2-03 (Motor No-Load Current) before making
changes to E2-01. An oPE01 error will be triggered if E2-01
< E2-03.
10 to 200%
of drive
rated
current
<9>
<10>
S
S
−
30E
E2-02
Motor Rated Slip
Sets the motor rated slip in Hertz.
Automatically set during rotational Auto-Tuning.
0.00 to
20.00
<10>
A
A
−
30F
B.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
367
B
Parameter List