5.5 E: Motor Parameters
E parameters cover V/f pattern and motor data settings.
u
E1: V/f Characteristics
n
E1-01: Input Voltage Setting
Set the input voltage parameter to the nominal voltage of the AC power supply. This parameter adjusts the levels of some
protective features of the drive (overvoltage, Stall Prevention, etc.).
NOTICE: Set parameter E1-01 to match the input voltage of the drive. Drive input voltage (not motor voltage) must be set in E1-01 for the
protective features of the drive to function properly. Failure to comply could result in improper drive operation.
No.
Parameter Name
Setting Range
Default
E1-01
<1>
Input Voltage Setting
155 to 255 V
230 V
<1> The setting range and default value shown here are for 200 V class drives. Double this for 400 V class units.
E1-01 Related Values
The input voltage setting determines the over-/undervoltage detection level and the operation levels of the braking transistor
as well as the KEB function and the overvoltage suppression function.
Voltage
Setting Value of
E1-01
(Approximate Values)
ov Detection
Level
BTR Operation
Level
Uv Detection Level
(L2-05)
Desired DC Bus
Voltage during KEB
(L2-11)
ov Suppression /
Stall Prevention
Level
(L3-17)
200 V Class
all settings
410 V
394 V
190 V
(single-phase = 160
V)
240 V
370 V
400 V Class
setting
≥
400 V
820 V
788 V
380 V
480 V
740 V
setting < 400 V
740 V
708 V
350 V
440 V
660 V
Note:
The braking transistor operation levels are valid for the drive internal braking transistor. If an external CDBR braking chopper is used, refer
to the instruction manual of that unit.
n
V/f Pattern Settings
The drive utilizes a set V/f pattern to determine the appropriate output voltage level for each relative to the frequency reference.
There are 15 different preset V/f patterns to select from with varying voltage profiles, saturation levels (frequency at which
maximum voltage is reached), and maximum frequencies. Additionally, one custom V/f pattern can be set up by programming
parameters E1-04 through E1-10.
V/f Pattern Setup for V/f Control
1.
Set the input voltage for the drive.
Refer to E1-01: Input Voltage Setting on page 169
2.
Set the V/f pattern by:
a) choosing one of the 15 preset V/f patterns (E1-03 = 0 to E).
b) select the custom V/f pattern (E1-03 = F, default setting).
3.
When using one of the 15 presets, E1-04 through E1-13 are automatically set. Refer to the description below.
For a custom V/f pattern, E1-04 through E1-13 must be adjusted manually.
Refer to V/f Pattern Settings E1-04 to
.
Open Loop Vector Control Setup for IM and PM Motors
In OLV only the user defined V/f pattern can be used.
Refer to V/f Pattern Settings E1-04 to E1-13 on page 172
.
n
E1-03: V/f Pattern Selection
This parameter can only be changed when the drive is operating in V/f Control. It allows the user to select the V/f pattern from
15 predefined patterns or to create a custom V/f pattern.
No.
Parameter Name
Setting Range
Default
E1-03
V/f Pattern Selection
0 to F
F
5.5 E: Motor Parameters
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
169
5
Parameter Details