2.
Setting E1-11 to 0 disables both E1-11 and E1-12 and the above conditions do not apply.
3.
To make the V/f pattern a straight line set E1-09 = E1-07. In this case the E1-08 setting is disregarded.
4.
E1-03 is unaffected when the drive is initialized using parameter A1-03, but the settings for E1-04 through E1-13 are returned to their
default values.
u
E2: Motor 1 Parameters
These parameters contain the most important motor data needed for optimal motor control. The parameters are set automatically
during Auto-Tuning. Set the parameters manually when Auto-Tuning cannot be performed.
n
E2-01: Motor Rated Current
Set E2-01 to the full load amps (FLA) stamped on the motor nameplate. During Auto-Tuning the value must be entered to
parameter T1-04. If Auto-Tuning completes successfully, the value entered will automatically be saved to E2-01.
No.
Parameter Name
Setting Range
Default
E2-01
Motor Rated Current
10% to 200% of the drive
rated current.
(unit: 0.01 A)
Depending on
o2-04
Note:
1.
Display is in the following units: BA0001 to BA0018, 2A0001 to 2A0040, and 4A0001 to 4A0023: 0.01 A units.
2A0056 to 2A0069, 4A0031 to 4A0038: 0.1 A units.
2.
Change E2-01 only after changing the value set to E2-03. Setting E2-01 < E2-03 will trigger an oPE02 error.
n
E2-02: Motor Rated Slip
Sets the motor rated slip in Hz. This value is automatically set during Rotational Auto-Tuning.
No.
Parameter Name
Setting Range
Default
E2-02
Motor Rated Slip
0.00 to 20.00 Hz
Depending on
o2-04
If Auto-Tuning cannot be performed calculate the motor rated slip using the information written on the motor nameplate and
the formula below:
E2-02 = f - (n x p)/120
(f: rated frequency (Hz), n: rated motor speed (r/min), p: number of motor poles)
n
E2-03: Motor No-Load Current
Set E2-03 to the motor no-load current at rated voltage and rated frequency. If Rotational Auto-Tuning completes successfully,
this value is automatically calculated. If Auto-Tuning cannot be performed, contact the motor manufacturer for information
about the no-load current.
No.
Parameter Name
Setting Range
Default
E2-03
Motor No-Load Current
0 to [E2-01]
(unit: 0.01 A)
Depending on
o2-04
Note:
Display is in the following units: BA0001 to BA0018, 2A0001 to 2A0040, and 4A0001 to 4A0023: 0.01 A units.
2A0056 to 2A0069, 4A0031 to 4A0038: 0.1 A units.
n
E2-04: Number of Motor Poles
Set the number of motor poles to E2-04. This value must be entered during Auto-Tuning, and will automatically be saved to
E2-04 if Auto-Tuning completes successfully.
No.
Parameter Name
Setting Range
Default
E2-04
Number of Motor Poles
2 to 48 poles
4 poles
n
E2-05: Motor Line-to-Line Resistance
Sets the line-to-line resistance of the motor stator winding. If the Auto-Tuning completes successfully, this value is
automatically calculated. Remember this value must be entered as line-line and not line-neutral.
No.
Parameter Name
Setting Range
Default
E2-05
Motor Line-to-Line Resistance
0.000 to 65.000 Ω
Depending on
o2-04
Note:
The setting range becomes 0.00 to 130.00 when using BA0002, 2A0002, 4A0001 and smaller.
5.5 E: Motor Parameters
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
173
5
Parameter Details