22 | RMB/ENERGIE GmbH
Technical data
Manual neoTower
®
Power Storage | (02/2022)
Technical data sheet neoTower
®
Power Storage Unit
BSS (Battery Storage System)
Version
BSS 7
BSS 11
BSS 21
Battery storage size (gross) [kWh]
7,1
10,7
21,3
Max. output power [VA]
3000
5000
10000
Max. efficiency [%]
n.a.
n.a.
n.a.
Continuous charging power [VA]
1700
3400
6700
Connections
2x 230 V (AC in)
2x 230 V (AC out)
1x 48 V (DC)
Cable cross section (50m max.)
2.5mm², 16A
4mm², 25A
4mm², 25A
PV connection
Storage function
Cooling principle
Operating modes
Measurements
Display
Protection class
IP20
IP20
IP20
Operating temperature [°C]
5-30
5-30
5-30
Humidity [%]
max. 95
max. 95
max. 95
Unit consumption [W]
11
18
36
Visualisation
CHP panel
CHP panel
CHP panel
Weight [kg]
222
267
469
Number of cabinets
(1)
1
1
2
Dimensions per cabinet (LxWxH) [mm]
Manufacturer
Power [kW]
3
5
10
Manufacturer
Gross capacity
2x 3552 Wh / 74 Ah
3x 3552 Wh / 74 Ah
6x 3552 Wh / 74 Ah
Operating voltage [V]
48
48
48
Cell type
LiFePo4
LiFePo4
LiFePo4
Efficiency [%]
90-95
90-95
90-95
Safety
Emissions
(1) The cabinets must always be positioned side by side.
Deviating values depending on ambient and operating conditions.
Subject to technical modifications, design variations and errors.
Standards and directives
Pylontech
1x 230 V (AC in)
1x 230 V (AC out)
1x 48 V (DC)
Inverter
VDE-AR-N 4105:2018-11
EN-IEC 60335-1, EN-IEC 60335-2-29
EN-IEC 62109-1, EN-IEC 62109-2
EN 55014-1, EN 55014-2
EN-IEC 61000-3-2, EN-IEC 61000-3-3
IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3
Battery modules
Victron
Mains parallel
Zero reference control via CHP
600 x 600 x 2.000
General
Fan ventilation
Mains replacement and network-forming standalone operation
Per phase current and power measurement
LED display on the unit
RMB/ENERGIE GmbH • Hauptstrasse 543a • 26683 Saterland • Phone.: +49 4498 92288-0 • Fax: +49 4498 92288-66
[email protected] • www.rmbenergie.com • Valid as of February 2022 Page: 1 of 1
8. Technical data
8.1 Technical data sheet BSS