22
4. COMMUNICATION REFERENCE TABLE
4.2: Function code 04
Reference
No.
FNC
Code
R/W
Data name
Setting range
(in-transmission)
30101
04
R
Current temp monitor
(PV)
K: -30
℃
to 610
℃
R: -30
℃
to 1210
℃
T: -200
℃
to 210
℃
PT1: -110
℃
to 110
℃
PT2: -200
℃
to 410
℃
◆
Refer to main unit instruction manual for above
sensors.
+over-range: 32767
-over-range: -32768
PV decimal point
30102
04
R
PV decimal position
DP.0/DP.1 (0/1)
30103
04
R
In-operation target temp
(SV)
RUN SV (target temp in program operation)
-1999 to 9999
℃
0
℃
when READY
PV decimal point
30104
04
R
In-operation execute
temp (SV)
Execute temp (SV) in program operation
-1999 to 9999
℃
0
℃
when READY
PV decimal point
30105
04
R
Output MV (MV)
-10.0 to 110.0%
30107
04
R
RUN/READY
status monitor
High order byte
0: Fixed temp operation
1: Fixed temp auto start
2: Fixed temp auto stop
3: Program operation
4: Program auto start
Low order byte
0 = READY (standby)
1 = RUN (running)
2 = END (end)