4. COMMUNICATION REFERENCE TABLE
External communication
When using external communication option on any unit, access by anything other
than the following reference addresses, may cause equipment malfunction. Do not
attempt to use any reference address, code or utility other than those given below
or as recommended by Yamato Scientific Co., Ltd. Do not access functions that are
not mentioned in the controller keys operation (see main unit instruction manual).
Unit may malfunction or become out of control.
4.1: Function code 03/06
TYPE V Controller Communication Reference table; items with “*” are not applicable by model
Reference
No.
FNC
Code
R/W
Data name
Setting range
(in-transmission)
Initial
value
Remarks
40001
03
06
R
W
Fixed temp operation
SV setting
SLL-SLH
0.0
℃
◆
Corrected within the
range between SLL and
SLH
40002
03
06
R
W
Fixed temp auto start
SV setting
SLL-SLH
0.0
℃
◆
Corrected within the
range between SLL and
SLH
40003
03
06
R
W
Fixed temp auto start
time/timer select
Timer/time
(0/1)
Timer
40004
03
06
R
W
Fixed temp auto start
time setting (H)
00-99
(0-99)
00
H: hour
40005
03
06
R
W
Fixed temp auto start
timer setting (L)
00-59
(0-59)
00
L: minute
40006
03
06
R
W
Fixed temp auto start
time setting (H)
00-23
(0-23)
00
H: hour
40007
03
06
R
W
Fixed temp auto start
time setting (L)
00-59
(0-59)
00
L: minute
40008
03
06
R
W
Fixed temp auto stop
SV setting
SLL-SLH
0.0
℃
◆
Corrected within the
range between SLL and
SLH
40009
03
06
R
W
Fixed temp auto stop
timer/time select
Timer/time
(0/1)
Timer
40010
03
06
R
W
Fixed temp auto stop
timer setting (H)
00-99
(0-99)
00
H: hour