![Yamato FO 100 Скачать руководство пользователя страница 20](http://html.mh-extra.com/html/yamato/fo-100/fo-100_instruction-manual_905271020.webp)
18
Operation Method
Program Operation
This operation is used to change the temperature according to the setting temperature and time.
Program types
Six patterns of program types maximum can be input.
PrG1 -
1 program pattern using 30 steps maximum can be created.
PAt1
PrG2
PAt2
2 program patterns using 15 steps maximum can be created.
PAt1
PAt2
PrG3
PAt3
3 program patterns using 10 steps maximum can be created.
Before inputting program
…
Input program patterns before program operation.
①
Check the number of steps in a created program and their setting temperature/time. Use the
program preparation form in pages 26 and 27 to check.
②
Check the temperature rise/fall capability of the unit. Set the time within the capability above.
Suppose, for instance, that in the unit which has capability of increasing or decreasing
temperature by 3
℃
within ten minutes, about 35 minutes is needed to increase or decrease
temperature by 10
℃
from current temperature
(Refer to the "Temperature Rise/Fall Curve (Reference)" on the pages 23 to 25.)
Repeat function:
Repeat function is useful in case the operation uses the program repeating the same program
steps. Refer to page22 for the function.
③
Check if the controller has sufficient free pattern for the number of steps to be created. The steps,
however, using the repeat function mentioned above are not counted.
Temp.
Time
△
Stop
△
Start