Chapter 1. OVERVIEW AND PRODUCT

CONFIGURATION

n Overview

The FRS100 Multiburner Control features built-in safe-start circuitry. To ensure
safety, this circuitry prevents ignition if a failure is detected at startup, and shuts
off the fuel line if the flame is interrupted during operation. Combined use with an
ultraviolet flame detector or flame rod enables batch operation of burners.

n Features

• The start check function inspects the flame detector and flame relay body at

startup to ensure safe operation. If an abnormality is found, ignition is
prevented.

• The controller is designed to be compact, and can be plugged into the wiring

sub-base. The sub-base can be mounted by screws or onto a DIN rail.

• The power supply state and ignition detection can be read easily from the LEDs

on the front display. Completion of the start check is indicated by the LED on
the center of the body behind the front cover.

• Flame voltage output (0 to 5Vdc) can be checked at the dedicated terminal by a

general-purpose tester, or continuously monitored by a panel meter or recorder.

• The controller has a dedicated connector so that the optional FRS60A Flame

Meter can be attached.

n Model listing

1-1

Model No.

Rated Power Supply

FRS100B100

100Vac

50 / 60Hz

FRS100B200

200Vac

50 / 60Hz

FRS100B104

100Vac

50 / 60Hz

FRS100B204

200Vac

50 / 60Hz

FRS100C100

100Vac

50 / 60Hz

FRS100C200

200Vac

50 / 60Hz

FRS100C104

100Vac

50 / 60Hz

FRS100C204

200Vac

50 / 60Hz

FRS100C150

100Vac

50 / 60Hz

FRS100C250

200Vac

50 / 60Hz

FRS100C154

100Vac

50 / 60Hz

FRS100C254

200Vac

50 / 60Hz

Power

Consumption
3W max.

7W max.

7W max.

Flame Failure

Response

3 ±1s
(flame voltage 2V)

2s max.
(flame voltage 2V)

3 ±1s
(flame voltage 4.2V)

2s max.
(flame voltage 4.2V)

3 ±1s
(flame voltage 3.5V)

2s max.
(flame voltage 3.5V)

Flame Detector

Flame Rod

C7007A, C7008A
Ultraviolet Flame

Detector

C7012A, C7012C
Minipeeper
Ultraviolet Flame
Detector
C7035A, C7027A

Model

Standard model

High-sensitivity
model

Содержание azbil FRS100

Страница 1: ...This manual contains information for ensuring the correct use of the FRS100 It also provides necessary information for installation maintenance and trou bleshooting This manual should be read by thos...

Страница 2: ...use this product in applications where human safety may be put at risk RESTRICTIONS ON USE NOTICE 1999 Yamatake Corporation ALL RIGHTS RESERVED Be sure that the user receives this manual before the p...

Страница 3: ...t warns the user of the danger of electric shock White circles with a diagonal bar notify the user that specific actions are prohibited to prevent possible danger These icons graphically represent the...

Страница 4: ...e of this control Prevent the pilot and main burner ignition times from exceeding the burner ignition time which the equipment manufacturer specifies Excessively long ignition time might cause fuel to...

Страница 5: ...esult fuel will continue to be supplied causing a very serious explosion hazard This control has extremely important functions for safe operation of equipment Follow the instructions in the user s man...

Страница 6: ...Flame Detector to terminal 5 and the white lead to terminal 6 If the power is turned ON with the Minipeeper Ultraviolet Flame Detector wired wrongly the UV tube might be damaged When equipment is rest...

Страница 7: ...manual Handling Precautions Handling Precautions indicate items that the user should pay attention to when handling the FRS100 Note Notes indicate information that might benefit the user 1 2 3 Number...

Страница 8: ...lame detector 2 6 Wiring the solenoid valve 2 7 Wiring the surge absorber 2 8 Chapter 3 EXPLANATION OF OPERATION Manual ignition intermittent pilot 3 1 Burner flame monitoring 3 3 Chapter 4 ADJUSTMENT...

Страница 9: ...on the center of the body behind the front cover Flame voltage output 0 to 5Vdc can be checked at the dedicated terminal by a general purpose tester or continuously monitored by a panel meter or reco...

Страница 10: ...C C7007A C7008A 1 2 Chapter 1 OVERVIEW AND PRODUCT CONFIGURATION Ultraviolet Flame Detector Flame Rod Name Model No C7035A C7027A Minipeeper Ultraviolet Flame Detector Name Model No FRS50A100 123514B...

Страница 11: ...POWER FLAME PRS 100 FLAME RELAY POWER FLAME PRS 100 Above 50mm min 20mm min Below 20mm min 20mm min FLAME RELAY POWER FLAME PRS 100 CAUTION Do not mount this control in the following locations Near c...

Страница 12: ...il fixing plate to fix onto the DIN rail 4 Wire the subbase terminals as instructed in 2 2 Wiring 5 Pull the bottom of the controller cover downwards to remove 6 Press the controller into the subbase...

Страница 13: ...Pull the bottom of the controller cover downwards to remove 5 Press the controller into the subbase with the display facing upwards 6 Tighten the mounting screw on the center of the body to fix onto t...

Страница 14: ...ncy as indicated on the Model No label is supplied to the controller When configuring control circuits select reliable timers and auxiliary relays as necessary for use as additional functions Be sure...

Страница 15: ...espectively Accordingly connect the voltage side H to terminal 1 and the ground side G to terminal 2 Burner flame monitoring Handling Precautions The power supply is marked H and G for the voltage and...

Страница 16: ...le lead length Approx 30m Wiring between the C7012A C Ultraviolet Flame Detector and the FRS100B Permissible lead length Type of signal lead High frequency coaxial cable 5C2V 7C2V Permissible lead len...

Страница 17: ...ure above and if a ground fault occurs Accordingly the solenoid valve will open regardless of the flame relay causing fuel discharge Voltage side H Ground side G Ground fault Burner Combustion unit Po...

Страница 18: ...utions Use a JIS C 3306 0 75mm2 power lead lead diameter 0 18 30 strand or higher for wiring to the power supply Attach a Faston receptacle 187 made by AMP to one end of the power lead and make the wi...

Страница 19: ...p False Flame Operation Input Operation input terminals 7 3 Ignition switch Output Ignition transformer Pilot valve Main valve Indication POWER LED FLAME LED Start check LED 1K relay Combustion lamp F...

Страница 20: ...switch ON Pilot operations burner normally lights When the flame detector detects the pilot burner flame in 5 to 10 seconds the 2K relay turns ON the FLAME LED lights up Ignition switch OFF The pilot...

Страница 21: ...minals 3 4 turn ON The FLAME LED lights up in sync with terminals 3 4 turn ON Normal Operation Input Operation input terminals 1 7 Flame detection F G terminals 5 6 Output Start check output terminals...

Страница 22: ...s manual WARNING Prevent the pilot and main burner ignition times from exceeding the burner ignition time which the equipment manufacturer specifies Excessively long ignition time might cause fuel to...

Страница 23: ...h burner under various conditions at startup normal operation etc 2 When measuring the flame voltage insert the tester probes into the holes to connect to terminals A and B at the bottom front of the...

Страница 24: ...the combustion lamp went out Chapter 4 ADJUSTMENTS FOR TRIAL OPERATION WARNING If the flame detector is set so that it detects a pilot flame that is too small to ignite the main burner this control w...

Страница 25: ...is probably that the pilot flame is too small Increase the size of the pilot flame and carry out the following adjustment Either slightly take the monitor line of the flame detector away from the axi...

Страница 26: ...If the FLAME LED lights up carry out the following adjustment referring also to the equipment user s manual Move the position of the ultraviolet flame detector or ignition spark rod so that the ultrav...

Страница 27: ...hold down the ignition switch Flame failure during normal combustion 1 Open the manual fuel valves of the pilot and main burner 2 Press the ignition switch to start operation 3 After the ignition seq...

Страница 28: ...Failure to do so might cause electric shock Do not touch the terminals on this control Doing so might result in an electric shock Do not touch terminal F or the flame detector cable connected to termi...

Страница 29: ...the plug end 121708 flame simulator Contact the terminal 5 to the F lug Contact the terminal 6 to the G lug Handling Precautions Keep the check time short and remove the simulator promptly after comp...

Страница 30: ...ons when directly mounted on panel Insulation Resistance 50M min between terminals and ground terminal by 500Vdc megger Dielectric Strength No failure after applying 1500Vac for 1min or 1800Vac for 1s...

Страница 31: ...s when FRS100 is mounted on FRS50A100 DIN rail Cover Unit mm Subbase FRS50A100 sold separately FRS100 Chapter 6 SPECIFICATIONS 1 Dimensions required for mounting and removing body 2 Dimensions require...

Страница 32: ...6 3 FRS50A100 subbase Chapter 6 SPECIFICATIONS DIN rail DIN rail mounting plate Subbase mounting holes 2 M3 5 terminal screw 8...

Страница 33: ...9m s 2 Mar 2003 6th Edition RESTRICTIONS ON USE changed 4 2 Insulation resistance corrected 100MW to 50MW Feb 2004 7th Edition ii R4334A was deleted from the 3rd item iii 5 1 One item was added to war...

Страница 34: ...hange without notice Advanced Automation Company 1 12 2 Kawana Fujisawa Kanagawa 251 8522 Japan URL http www azbil com Printed on recycled paper 07 Printed in Japan 1st Edition Issued in Oct 1999 K 13...

Отзывы: