3-3
■
Burner flame monitoring
Chapter 3. EXPLANATION OF OPERATION
●
Operation
• When the operation contact turns ON, the 1K relay turns ON at completion of
the start check, and terminals 3-8 turn ON. (The start check LED lights up in
sync with terminals 3-8 turn ON).
• When the flame is detected, the 2K relay turns ON, and terminals 3-4 turn ON.
(The FLAME LED lights up in sync with terminals 3-4 turn ON).
Normal Operation
[Input]
Operation input (terminals 1-7)
Flame detection F-G (terminals 5-6)
[Output]
Start check output (terminals 3-8)
Flame output (terminals 3-4)
[Indication]
POWER LED
FLAME LED 2K
Start check LED
False Flame Operation
[Input]
Operation input (terminals 1-7)
Flame detection F-G (terminals 5-6)
[Output]
Start check output (terminals 3-8)
Flame output (terminals 3-4)
[Indication]
POWER LED
FLAME LED
Start check LED
Flame failure response