background image

Copyright ©2018, 2020 ASSA ABLOY Access and Egress Hardware Group, Inc. All rights reserved. Reproduction in whole or in 
part without the express written permission of ASSA ABLOY Access and Egress Hardware Group, Inc. is prohibited.

For technical support contact Yale

®

 at 800.438.1951 x5033 or [email protected]

4

Delayed Egress

Installation Instructions

7100, 7200 Series Exit Device

80-9470-0162-000 10/20

1

Panic and Fire Rated Devices

1.  Check device for shipping damage prior to installation and make sure all parts are on hand.

2.  Identify options provided with device.

3.  Identify model, type and hand of trim if applicable (see exit device and trim instructions for 

reversing hands).

4.  Contact hardware supplier if device is damaged or missing parts.

a

Checklist

b

Required Components 

(Numbered list correlates with numbers in Fig

ure 1)

c

Optional Components 

(Numbered list correlates with numbers in Fig

ure 1)

1.  Delayed Egress Exit Device

2.  24VDC UL Listed Regulated and Filtered Power Supply with Fire Alarm Interface (recommend 

Securitron BPS 24-1 or 24-2 (UL294 Listed), depending on requirements). Power supply is NOT to 
be used in UL603 Burglar Alarm System.

3.  Power transfer UL or ULC listed (2-10 wire depending on system)-Securitron (EPT) or equivalent.

4.  Sign (MUST BE INSTALLED ON DOOR ABOVE DEVICE).

NOTE: The delayed egress system is to be installed in accordance with NFPA 101.

5. Remote 

Annunciator

6.  Door Position Switch (DPS)

7. Standard 

Trim

8. Electrified 

Trim

9.  Device and Trim Cylinder

d

Electrical Specifications*

Input Voltage 24VDC (+/-10%)

Wire Size:

18 AWG Min (up to 100')

Signal or Control 22AWG Min

Power Consumption:

Standard Device - 500mA

Device with Electric Trim - 1.5A

*Follow Local Electrical Codes for Wiring.

NOTE: Components shown do not reflect all possible applications. Consult 
manufacturer for special applications.

Figure 1  

6.

4.

PUSH UNTIL ALARM

SOUNDS. DOOR CAN BE

OPENED IN 15 SECONDS.

3.

5.

1.

8.

7.

9.

115 VAC
1 or 2A
60 Hz

Fire
Alarm
Circuit
Required

Or

2.

Содержание 7100 Series

Страница 1: ... For more information go to www P65warnings ca gov Attention Installer Any retrofit or other field modification to a fire rated opening can potentially impact the fire rating of the opening and Yale Locks Hardware makes no representations or warranties concerning what such impact may be in any specific situation When retrofitting any portion of an existing fire rated opening or specifying and inst...

Страница 2: ...ectrical Specifications 4 2 End Cover and PC BoardAssembly 5 3 DIP Switch Settings 6 4 Installation of End CoverAsssembly to Device 7 5 Device Mounting 8 6 Wiring Layout Input Output Wiring Descriptions 9 7 ElectroLynx Connector System forAll Electrical Installation 10 8 ElectroLynx Wiring Options Overview with QC8 Hinge 11 9 Installing Delayed Egress Exit Device 12 10 ElectroLynx Wiring Options O...

Страница 3: ...t Device Installation Instructions 80 9470 0162 000 10 20 TOC Table of Contents 16 Wiring Diagram Single Door with Remote Inputs Monitoring Outputs 21 17 Wiring Diagram O Trim Monitor Entry with External Door Position Switch 22 18 Wiring Diagram 690F ElectricalTrim Control 22 19 Wiring Diagram 691F ElectricalTrim Control 23 20 Operating Instructions 23 21 Additional Options Non ElectroLynx Wiring ...

Страница 4: ...ates with numbers in Figure 1 1 Delayed Egress Exit Device 2 24VDC UL Listed Regulated and Filtered Power Supply with Fire Alarm Interface recommend Securitron BPS 24 1 or 24 2 UL294 Listed depending on requirements Power supply is NOT to be used in UL603 Burglar Alarm System 3 Power transfer UL or ULC listed 2 10 wire depending on system Securitron EPT or equivalent 4 Sign MUST BE INSTALLED ON DO...

Страница 5: ...153 x 2160 cam 1 1 8 mortise cylinder For cylinders over 1 1 8 use Yale 1765 Series cylinder ring Typical Mortise Cylinder 1 Trim device to proper length as required 36 Exit Device 1 maximum can be trimmed 48 Exit Device 6 maximum can be trimmed 2 Carefully slide circuit board assembly into end Cover to ensure indicator light LED is not bent 3 Insert mortise cylinder into end cover with keyway hor...

Страница 6: ...ng cylinder key or remote reset signal If door DPS is opened then closed before selected time expires the device will rearm immediately If DPS is not used is bypassed with S2 7 ON the door will rearm immediately after 5 10 20 or 40 sec whether the door is open or closed with either S2 8 ON or OFF Ensure eight S2 Dip Switches are set per application before moving on to the next page of instructions...

Страница 7: ...plication see previous page 3 Slide end cover assembly into device making sure not to pinch or crimp wires 4 Connect device lock assembly harness to connector J1 Place wire connectors and excess wire between end cover and P C board Figure 3 Device End View 5 Check all connections before proceeding 6 Proceed to device mounting see packed instructions Connector J2 To Power Transfer Hinge Optional O ...

Страница 8: ...01 for wire access hole location 2 Feed wires from power transfer through wire access hole in door Figure 4 3 When required mount outside trim to door see trim installation instructions 4 Mount device to door see device installation instructions 5 Do not install end cap until device has been wired and tested for operation See wiring diagrams 6 Check mechanical operation and proceed to wiring diagr...

Страница 9: ...elay de energizes contact is closed same as Power off state 4 NC EGND Orange Earth Ground connection to PCB mounting plate via ring terminal 5 3 Output Blue Alarm Relay Output J5 jumper Selectable NO NC contact that changes state when alarm cycle has been activated Default shipped position jumper is on NO contact setting Power off contact is NO or NC as per jumper selection Powered armed Relay ene...

Страница 10: ...ice per instruction sheet provided 2 Plug exit device connector into raceway connector in door Feed through 1 25mm hole in door Install rail mounting end clamp bracket with two 2 screws supplied Install end cap 3 Plug raceway connector from edge of door into electric hinge connector and feed wires back through door prep Mount electric hinge to door A If wiring now wire frame side wires to wires on...

Страница 11: ...tail harness is per facility wiring requirement 2 For an ElectroLynx system go to function or monitor page s with your device 3 Combinations of certain monitors can be used in each device These instructions detail installation of each monitor separately ElectroLynx Connector System Notes System is designed to be installation friendly with plug connectors from electric hinge through door to device ...

Страница 12: ...alelocks com 12 Delayed Egress Installation Instructions 7100 7200 Series Exit Device 80 9470 0162 000 10 20 9 Installing Delayed Egress Exit Device Figure 6 Refer to Figure 6 for delayed egress exit device installation wiring NOTE For ElectroLynx Hinge Connector System Follow Section 6 wiring instructions For non ElectroLynx door Remove connector at end of exit device and connect to incoming wire...

Страница 13: ...re REQUIRED 12 wires max If external DPS wiring is REQUIRED Set PCBA Dip Switch S2 7 OFF If LBM Trim Monitor OR Electrified Trim Options are REQUIRED 10 ElectroLynx Wiring Options Overview with QC12 Hinge Refer to Figure 7 on page 14 for O Monitor Trim Actuated SPDT Switch wiring NOTE Switch wiring max load 2A 28VDC Wire must be protected from abrasion For use with Class II circuits only For Elect...

Страница 14: ...ess written permission of ASSA ABLOY Access and Egress Hardware Group Inc is prohibited For technical support contact Yale at 800 438 1951 x5033 or support yalelocks com 14 Delayed Egress Installation Instructions 7100 7200 Series Exit Device 80 9470 0162 000 10 20 10 ElectroLynx Wiring Options Overview with QC12 Hinge continued Figure 7 ...

Страница 15: ...33 or support yalelocks com 15 Delayed Egress 7100 7200 Series Exit Device Installation Instructions 80 9470 0162 000 10 20 11 ElectroLynx Wiring Deed with O Trim Monitor Option and QC12 Hinge QC12 Hinge Field Wiring Options Wiring to 8 pin and 4 pin connectors is REQUIRED 12 wires max If external DPS wiring is NOT REQUIRED set PCBA Dip Switch S2 7 ON If external DPS wiring is REQUIRED set PCBA Di...

Страница 16: ... permission of ASSA ABLOY Access and Egress Hardware Group Inc is prohibited For technical support contact Yale at 800 438 1951 x5033 or support yalelocks com 16 Delayed Egress Installation Instructions 7100 7200 Series Exit Device 80 9470 0162 000 10 20 11 ElectroLynx Wiring Deed with O Trim Monitor Option and QC12 Hinge continued Mechanical Trim ...

Страница 17: ...ied Trim ET Option and QC12 Hinge QC12 Hinge Field Wiring Options Wiring to 8 pin and 4 pin connectors is REQUIRED 12 wires max If external DPS wiring is NOT REQUIRED set PCBA Dip Switch S2 7 ON If external DPS wiring is REQUIRED set PCBA Dip Switch S2 7 OFF Supplied with DEED when ordered Fail Safe or Fail Secure Electrified Trim ET Requires field to route two wires from ET through the chassis an...

Страница 18: ...tact Yale at 800 438 1951 x5033 or support yalelocks com 18 Delayed Egress Installation Instructions 7100 7200 Series Exit Device 80 9470 0162 000 10 20 13 ElectroLynx Wiring Deed with S Latchbolt Monitor Option and QC12 Hinge QC12 Hinge Field Wiring Options Wiring to 8 pin and 4 pin connectors is REQUIRED 12 wires max If external DPS wiring is NOT REQUIRED set PCBA Dip Switch S2 7 ON If external ...

Страница 19: ...ermission of ASSA ABLOY Access and Egress Hardware Group Inc is prohibited For technical support contact Yale at 800 438 1951 x5033 or support yalelocks com 19 Delayed Egress 7100 7200 Series Exit Device Installation Instructions 80 9470 0162 000 10 20 Mechanical Trim 13 ElectroLynx Wiring Deed with S Latchbolt Monitor Option and QC12 Hinge continued ...

Страница 20: ... Details are typical for all opening materials both hands This preparation is an addition to preparation shown on device template See device template to locate centerline Shields for wiring access recommended for insulated and composite doors Locate and prepare wiring access holes when installing device Vertical Reference Horizontal Reference Hinge Edge Detail INSIDE FACE OF DOOR Clear Channel Acc...

Страница 21: ...t touching device push bar rim will not affect alarm if a door position switch is not being used Refer to DPS wiring if necessary To NC Fire Alarm Contacts 120 VAC Securitron BPS Power Supply Wire Transfer Hinge Connector J2 Device QC8 24VDC Connect to EGND Connect to EGND 24VDC ALR NO NC BLU EGND ORG QC8 Connect EGND within BPS Power Supply or Local Building Ground 16 Wiring Diagram Single Door W...

Страница 22: ...h Door Position Switch DPS made by other manufacturers Operation Door Position Switch DPS is used to activate alarm when door has been forced open It also prevents device from being armed when door is propped open O trim monitor switch when activated will bypass unit and allow entry Unit must be manually reset for rearming with cylinder key Figure 12 NOTE Requires O trim monitor switch on device f...

Страница 23: ...test sequence is as follows Cover LED is RED for 2 seconds with horn sounding for 500ms Cover LED is then GREEN for 2 seconds followed by AMBER for 1 second with the 4 diagnositc LEDs illuminated Cover LED is RED and green diagnostic LED is illuminated The device is now armed which will not allow pushpad to retract latchbolt for immediate egress 2 If the device is not functioning refer to the Trou...

Страница 24: ...ation of momentary egress by cylinder key switch or external remote reset signal if the Door DPS is open beyond 40 seconds it will remain in momentary egress mode indefinitely and shall not enter alarm mode Then once the Door DPS is closed it will re arm immediately With S2 4 ON S2 5 ON S2 8 OFF for same scenario as above the device will enter alarm mode after 40 seconds if the Door DPS is still o...

Страница 25: ...pened before actual re arming of the device occures A DPS Door Position Switch is required for the BOCA option NOTE BOCA option is not suitable for installations in accordance with NFPA 101 22 BOCA 15 Second Delay and BOCA 30 Second Delay 23 NFPA 101 Requirements 30 Second Delay Upon depressing the pushpad for 3 seconds or longer the device will sound an audible beeping tone and allow the door to ...

Страница 26: ...fter troubleshooting contact your local hardware distributor or local Yale representative or contact Yale Problem Solution Power is applied but unit will not arm No red LED Check all connections on circuit board and wire harness Check for power 24VDC at power inputs black and red and check polarity Check wire transfer for any bad connections or broken wires Check power output at power supply Must ...

Страница 27: ...rd delay of 15 seconds 0r 30 second optional delay the rail solenoid de energizes and passage is allowed End cover LED is green with alarm at a steady tone which continues until reset by key switch 3 When a Door Status switch is used and the door is opened the Orange Diagnostic LED will turn ON which indicates that the door is not closed When not using a door status switch DIP switch position 7 mu...

Страница 28: ...sion of ASSA ABLOY Access and Egress Hardware Group Inc is prohibited Patent pending and or patent www assaabloydss com patents U S A Yale Locks Hardware Address 225 Episcopal Road Berlin CT 06037 4004 Tel 1 800 438 1951 Fax 1 800 338 0965 yalecommercial com Canada ASSA ABLOY Door Security Solutions Canada Address 160 Four Valley Drive Vaughan Ontario L4K 4T9 Tel 1 800 461 3007 Fax 1 800 461 8989 ...

Отзывы: