External Pressure
sensor [also
Differential]
P1+
9
Power supply external 15
VDC
15VDC, Ʃ max. 100 mA
P1-
10 External sensor 4-20 mA input
4÷20 mA
External
Start/Stop
START
11 External ON/OFF input reference
Default short circuited Pump is enabled
to RUN
STOP
12 External ON/OFF input
External Lack of
Water
LOW+
13 Lack water input
Default short circuited
Lack of water detection: enabled
LOW-
14 Low water reference
Communication
Bus
B1
15 RS485 port 1: RS485-1N B (-)
ACT, HCS control mode: RS 485 port1 for
external communication
MSE, MSY control mode: RS 485 port 1
for multi-pump systems
A1
16 RS485 port 1: RS485-1P A (+)
GND
17 Electronic GND
Communication
Bus
B2
18
RS485 port 2: RS485-2N B (-) active
only with optional module
RS 485 port2 for external
communication
A2
19
RS485 port 2: RS485-2P A (+) active
only with optional module
GND
20 Electronic GND
Fault signal
C
25 COM - error status relay
In case of power cables: use the M20
cable gland
Closed: error
Open: no error or unit off
NO
24 NO - error status relay
Motor running
signal
C
23 Common contact
In case of power cables: use the M20
cable gland
Open: motor in operation
Closed: motor not in operation
NO
22 Normally open contact
Auxiliary Voltage
Supply
15V
21 Auxiliary voltage 15 VDC
15VDC, Ʃ max. 100 mA
Analog input
0-10V
S+
20 Actuator mode 0-10 V input
0÷10 VDC
S-
19 GND for 0-10 V input
GND, electronic ground (for S+)
External Pressure
sensor [also
Differential]
P1+
18
Power supply external 15
VDC
15VDC, Ʃ max. 100 mA
P1-
17 External sensor 4-20 mA input
4÷20 mA
External pressure
sensor
P2+
16
Power supply external 15
VDC
15VDC, Ʃ max. 100 mA
P2-
15 Sensor 4-20 mA input
4÷20 mA
External Start/Stop
Start
14 External ON/OFF input
Default short circuited Pump is enabled
to RUN
Stop
13 External ON/OFF input reference
External Lack of
Water
LoW+
12 Lack water input
Default short circuited Lack of water
detection: enabled
LoW-
11 Low water reference
Communication
Bus
B2
10
RS485 port 2: RS485-2N B (-) active
only with optional module
RS 485 port2 for external communication
A2
9
RS485 port 2: RS485-2P A (+) active
only with optional module
GND
8 Electronic GND
Communication
Bus
B1
7 RS485 port 1: RS485-1N B (-)
ACT, HCS control mode: RS 485 port 1 for
external communication
Control mode MSE, MSY: RS 485 port 1
for multi-pump systems
A1
6 RS485 port 1: RS485-1P A (+)
GND
5 Electronic GND