P63
Multipump – Priority
This parameter shows the
pump priority value within
the multi-pump set.
This parameter displays the
following information:
Pr1 (Pr1) .. Pr3 (Pr3) or Pr0
(Pr0)
where:
• Pr1 .. PR3, indicate that
the pump is
communicating with
other pumps of the
displayed priority
order.
• Pr0 indicates that the
pump does not detect
the communication
with other pumps and
is considered alone in
the multi-pump bus
P64
Multipump – Revision
This parameter shows the
multi-pump protocol
revision value used.
6.6.7 Test run configuration
Test Run is a function that starts the pump after the last stop, in order to prevent it from
blocking.
Parameter number
Parameter name
Unit of measurement
Description
P65
Test Run – Time Start
[0-100]
G
h
This parameter sets the
time after which, once the
pump has stopped for the
last time, the Test Run will
start.
Default: 100 h.
P66
Test Run – Speed [Min-Max]
G
rpmx10
This parameter sets the
pump rotational speed for
the Test Run.
The Min and Max speeds
depend on the pump type.
Default: 200 rpmx10.
P67
Test Run – Time
Duration[0-180]
G
s
This parameter sets the
duration of the Test Run.
Default: 10 s.
6.6.8 Special parameters
Parameter number
Parameter name
Unit of measurement
Description
P68
Default Values Reload [NO,
rES]
If set to RES, after
confirmation this parameter
performs a factory reset that
reloads the default
parameter values.
6 System Setup and Operation
Smart Pump Range INSTRUCTION MANUAL
41