Item
Terminals
Ref.
Description
Notes
External pressure
sensor
P2+
16
Power supply external
15 VDC
15VDC,
Ʃ
max. 100
mA
P2-
15
Sensor 4-20 mA input 4-20 mA
External Start/Stop
Start
14
External ON/OFF
input
Default short circuited
Pump is enabled to
RUN
Stop
13
External ON/OFF
input reference
External Lack of Water LoW+
12
Low water input
Default short circuited
Lack of water
detection: enabled
LoW-
11
Low water reference
Communication Bus B2
10
RS485 port 2: RS485
port 2: RS485-2N B (-)
active only with
optional module
RS 485 port2 for
external
communication
A2
9
RS485 port 2: RS485
port 2: RS485-2P A
(+) active only with
optional module
GND
8
Electronic GND
Communication Bus B1
7
RS485 port 1:
RS485-1N B (-)
ACT, HCS control
mode: RS 485 port 1
for external
communication
Control mode MSE,
MSY: RS 485 port 1
for multi-pump
systems
A1
6
RS485 port 1:
RS485-1P A (+)
GND
5
Electronic GND
4 Installation
22
Smart Pump Range INSTRUCTION MANUAL