Pump Control
Part
Description
Level Device
The type of level device:
• Analog
• Open Bell
• Float Switches
Inter-Pump Delay
The delay, in seconds, between the start-stop, start-
start, or stop-stop levels.
High Level Runtime
The setting, in seconds, for the high-level runtime.
Applicable to the high-level float switch. If the
analog sensor is broken, this setting is used for
extra protection.
Low Level Block Time
The setting, in seconds, for the low-level blocktime.
Applicable to the low-level float switch. If the
analog sensor is broken, this setting is used for
extra protection.
Dry Run Protection
When the check box is selected, the pumps are not
allowed to run below the stop level, regardless of
delay settings.
Alternation Mode
The type of pump alternation mode:
• Fixed
• Standard
• Run Time
Maximum Pumps Running
• 1 Pump
• 2 Pumps
11 User Interface
Flygt FGC 400 Installation, Operation, and Maintenance
43